Setup and Wiring<br />

In order to set up and wire the functional example, it is absolutely<br />

necessary to consider the following note:<br />

Warning!<br />

In order to meet the requirements of <strong>Safety</strong> Category<br />

4, it is obligatory to read back the process signal to<br />

the actuator. Read back is not implemented in this<br />

example.<br />

The actuator in this example is an indicator light simulating<br />

a machine. If other actuators are used, read<br />

back has to be ensured by the user. The <strong>Safety</strong> <strong>Integrated</strong><br />

Functional Example AS-FE-I-007-V10-EN provides<br />

a detailed description of "Read back".<br />

An overview of the hardware structure<br />

The arrangement to implement the safety door interlock consists<br />

of a PROFIBUS configuration. A failsafe S7-CPU is used as<br />

DP master, an ET 200S as DP slave. Below, the wiring of conventional<br />

modules is shown only partly to provide greater clarity.<br />

PS<br />

307<br />

START<br />

STOP<br />

Machine<br />

runs<br />

CPU<br />

315F<br />

DP<br />

IM 151<br />

HF<br />

4DI HF<br />

F-DI<br />

PM-E<br />

4DI<br />

HF<br />

PM-E F-DO<br />

Hinge<br />

switch<br />

F-DI<br />

Actuator<br />

contact<br />

Actuaor<br />

<strong>Safety</strong><br />

position<br />

switch<br />

Monitoring<br />

unlocking<br />

Magnet<br />

Warning!<br />

A speed or standstill monitor for monitoring hazardous<br />

slowing down of a machine is simulated in this<br />

example with a button (NO) which is connected as<br />

single-channel to the failsafe input module (F-DI).<br />

When using real speed or standstill monitors they<br />

must be connected to the F-DI as double-channels<br />

(1oo2 evaluation).<br />

Note<br />

The "high feature" electronic modules can also be replaced<br />

by standard modules.<br />

Wiring of the hardware components<br />

Requirements: The power supplies are supplied with 230V AC.<br />

First check the addresses set at the hardware components<br />

listed below:<br />

Hardware<br />

component<br />

IM 151 High<br />

Feature<br />

Einzustellende<br />

Adress<br />

6 (PROFIBUS address)<br />

F-DI Switch position:<br />

1111111110<br />

F-DO Switch position:<br />

1111111101<br />

Note<br />

Can be changed<br />

The PROFIsafe addresses are<br />

automatically assigned during<br />

configuring the failsafe<br />

modules in STEP 7. The<br />

PROFIsafe addresses 1 to<br />

1022 are permissible. Please<br />

make sure that the setting at<br />

the address switch (DIL<br />

switch) on the side of the<br />

module corresponds to the<br />

PROFIsafe address in the<br />

hardware configuration of<br />

STEP 7.<br />

Note<br />

The DP interface of the CPU 315F must be connected<br />

with the DP interface of the IM 151 HF.<br />

Note<br />

The wiring of the hardware is illustrated below. In the<br />

following table, the hardware components occurring<br />

several times are numbered so they can be allocated in<br />

the subsequent wiring plan.<br />

Functional Example No. AS-FE-I-003-V10-EN 195<br />