Ex. No.<br />

9 Setup and Wiring<br />

In order to set up and wire the functional example, it is absolutely<br />

necessary to consider the following note:<br />

An overview of the hardware structure<br />

The arrangement for single or group shutdown consists of a<br />

PROFIBUS configuration. A failsafe S7-CPU is used as DP master,<br />

an ET 200S as DP slave.<br />

PS<br />

307<br />

START M1<br />

ACK all<br />

ACK (1)<br />

CPU<br />

315F<br />

DP<br />

START M2<br />

ACK (2)<br />

IM 151<br />

HF<br />

PM-E<br />

Emergency<br />

stop (1)<br />

Emergency<br />

stop (2)<br />

Emergency<br />

stop (all)<br />

Note<br />

One 4DI electronic module can be used instead of two<br />

2DI electronic modules. The "high feature" electronic<br />

modules can also be replaced by standard modules.<br />

Wiring of the hardware components<br />

2DI<br />

HF<br />

PM-E F-DO<br />

F-DI<br />

Requirements: The power supplies are supplied with 230V AC.<br />

First check the addresses set at the hardware components<br />

listed below:<br />

280 Functional Example No. AS-FE-I-009-V10-EN<br />

Contactor K1 Contactor K2 Contactor K3 Contactor K4<br />

Readback signals<br />

Note<br />

In order to meet the requirements of <strong>Safety</strong> Category 4, it is<br />

obligatory to read back the process signal to the actuator.<br />

Hardware<br />

component<br />

IM 151 High<br />

Feature<br />

Address<br />

to be set<br />

6 (PROFIBUS address)<br />

F-DI Switch position:<br />

1111111110<br />

F-DO Switch position:<br />

1111111101<br />

Circuit<br />

breaker<br />

K1<br />

K2<br />

Motor M1<br />

Y switch<br />

Note<br />

Load circuit 400V<br />

K3<br />

K4<br />

Can be changed<br />

Motor M2<br />

Y switch<br />

The PROFIsafe addresses are<br />

automatically assigned during<br />

configuring the failsafe<br />

modules in STEP 7. The<br />

PROFIsafe addresses 1 to<br />

1022 are permissible. Please<br />

make sure that the setting at<br />

the address switch (DIL<br />

switch) on the side of the<br />

module corresponds to the<br />

PROFIsafe address in the<br />

hardware configuration of<br />

STEP 7.