Ex. No.<br />

5.2<br />

Restrictions<br />

Caution<br />

Please take careful note that the two safety functions<br />

SLS and SS1 may not be used for loads that can drive<br />

the motor or loads that are continually in the regenerative<br />

mode.<br />

Elevating platforms, winders, wind turbines are examples<br />

of such loads that can drive motor or continually<br />

regenerate in to the line supply.<br />

An important prerequisite when using fail-safe functions<br />

is that the closed-loop control functions absolutely<br />

perfectly. The drive (system comprising the drive<br />

inverter + motor + driven load) must be engineered so<br />

that all operating situations of the particular application<br />

are always completely under control.<br />

Caution<br />

After the STO and SS1 safety functions have been activated<br />

there is no electrical isolation between the line<br />

power supply of the SINAMICS G120 and the motor.<br />

If this electrical isolation is required in your particular<br />

application, then you must install an appropriate line<br />

contactor upstream of the SINAMICS G120.<br />

488 Functional Example No. SD-FE-I-002-V10-EN