Ex. No.<br />

11 FB2 / Network 2<br />

Overview of the signals of the network<br />

Signal Source / Target Meaning<br />

ENABLE From network 1 Enable from emergency-stop<br />

circuit<br />

REQ_START From FB1 (standard Start requirement<br />

block)<br />

for ACTUATOR<br />

ACTUATOR To process (indicator Representative for a<br />

light)<br />

"hazardous load".<br />

Description of the network function:<br />

The ACTUATOR load is switched on if the ENABLE from the<br />

emergency-stop circuit is pending and the start requirement<br />

REQ_START is given.<br />

338 Functional Example No. AS-FE-I-011-V10-EN<br />

FB2 / Network 3<br />

Overview of the signals of the network<br />

Signal Source / Target Meaning<br />

TEST_IN From process („1“) Signal from F-DI "1" is<br />

constantly set at F-DI.<br />

TEST To process (indica- Only for demonstrator<br />

light)<br />

tion, no other function.<br />

Description of the network function:<br />

TEST is used to demonstrate passivation of the entire module.<br />

When there is no passivation, TEST is always switched on, as<br />

TEST_IN at the F DI is constantly supplied with "1".<br />

The TEST indicator light is only switched off if F-DI is passivated.