Ex. No.<br />

5.3<br />

Function Test<br />

After the hardware components have been wired and the S7<br />

and SIMOCODE pro projects have been downloaded, the assigned<br />

inputs and outputs can be checked for functionality.<br />

Assigned inputs and outputs<br />

No. HW component Terminal Symbol Signal (default<br />

value)<br />

1 EMERGENCY STOP input IN4 EMERGENCY<br />

STOP<br />

2 EMERGENCY STOP pushbutton<br />

contact 1<br />

3 EMERGENCY STOP pushbutton<br />

contact 2<br />

4 Acknowledge EMERGENCY STOP<br />

button<br />

Testing inputs and outputs<br />

168 Functional Example No. CD-FE-I-042-V10-EN<br />

Note Device<br />

1 EMERGENCY STOP<br />

activated at 0<br />

SIMO<br />

Y11 - Y12 1 3TK2823<br />

Y21 - Y22 1 3TK2823<br />

Y33 - Y34 0 3TK2823<br />

5 Contactor K1 14 K1 3TK2823<br />

6 Operational switching OUT1 Output 1 0 Start 3TK28 at 1 SIMO<br />

7 Operational switching star-delta OUT2 Output 2 0 Start 3TK28 at 1 SIMO<br />

8 ON button OP buttons ON OP<br />

9 OFF button OP buttons OFF OP<br />

No. Action Reaction Note<br />

1 Ensure that the EMERGENCY STOP pushbutton<br />

is released<br />

2 Press the Acknowledge EMERGENCY STOP<br />

button.<br />

3 Press the ON> or ON>> button on the<br />

SIMOCODE operator panel<br />

If the EMERGENCY STOP has been activated,<br />

the 3TK28 must be acknowledged. The contacts<br />

K1, K2 and K4 are closed.<br />

Contactor K1 responds and there is voltage<br />

on contact 24 of the 3TK28.<br />

Output OUT1 switches voltage to contactor<br />

K2, and the outputs OUT2 and OUT3 switch<br />

voltage to the contactors K4 and K3 as per<br />

star-delta switching.The contactors respond<br />

accordingly.<br />

4 Press the EMERGENCY STOP pushbutton. Contactors K1, K2 and K4 release, activation<br />

of the EMERGENCY STOP is signaled to<br />

SIMOCODE via contact 24 of the 3TK28.<br />

SIMOCODE switches outputs OUT1 and<br />

OUT2 to 0.<br />

5 Release the EMERGENCY STOP pushbutton.<br />

Contacts K1, K2 and K4 are closed<br />

6 Press the Acknowledge EMERGENCY STOP<br />

button.<br />

Contactor K1 responds and there is voltage<br />

on contact 24 of the 3TK28.<br />

3TK28 is acknowledged and the load<br />

can be started via SIMOCODE<br />

The motor runs<br />

The load is stopped safely<br />

SIMOCODE has activated the<br />

EMERGENCY STOP, no fault is signaled.<br />

3TK28 is acknowledged and the load<br />

can be started via SIMOCODE