Behavior when Emergency Stop is issued<br />

Emergency Stop is initiated using button S3 ("Emergency<br />

Stop"). This initiates that the drive is shut down according to<br />

stop Category 1 in compliance with EN 60204-1.<br />

■ A 0 signal is entered at contact 65 (controller enable) of the<br />

drive via the enable contacts of safety combination A1. The<br />

drive is immediately braked down to 0 speed and the pulses<br />

are cancelled. At the same time, the drop-out delay of timer<br />

relay K2a and the delay time of the safety relay A1 are<br />

started; the drive must have come to a standstill before<br />

they expire.<br />

Behavior when the protective doors are opened<br />

When the protective doors are opened, it is initiated that the<br />

drive is shut down according to stop Category 1 in compliance<br />

with EN 60204-1. It must be ensured that potentially hazardous<br />

motion must have come to a standstill before a person can<br />

reach the potentially hazardous area!<br />

■ A 0 signal is entered at contact 65 (controller enable) of the<br />

drive via the enable contacts of safety combination A2. The<br />

drive is immediately braked down to 0 speed and the pulses<br />

are cancelled. At the same time, the switch-out delay of<br />

time relay K2a is started and before this time has expired,<br />

the drive must have come to a standstill.<br />

■ The internal safety relay of the drive is no longer energized<br />

after the drop-out delay time of time relay K2a has expired<br />

(1st shutdown path!).<br />

Powering-up and powering-down the drive<br />

The drive can be started or stopped when the protective doors<br />

are closed and Emergency Stop button S3 is released.<br />

■ When pressing button S2 ("On"), safety combination A1 is<br />

brought into the operational state. The internal line contactor<br />

of the rectifier unit is energized<br />

■ When pressing button S2 ("On"), contactor K3 is energized<br />

and latches; time relay K2a is simultaneously energized.<br />

The internal safety relay is energized and a 1 signal is<br />

entered at contact 65 (controller enable) of the drive. The<br />

drive restarts.<br />

■ The internal safety relay of the drive is no longer energized<br />

after the drop-out delay time of time relay K2a has expired<br />

(1st shutdown path!).<br />

■ After opening the safely delayed enable contact of safety<br />

combination A1, the internal line contactor of the rectifier<br />

unit is no longer energized and the drive is electrically isolated<br />

from the line supply (2nd shutdown path!).<br />

■ The checkback signal of the internal line contactor of the rectifier<br />

unit is monitored in the on circuit of safety combination<br />

A1. If the contactor does not drop-out due to an incorrect<br />

function, then the drive is prevented from restarting after an<br />

Emergency Stop.<br />

■ Before the selected delay time of safety combination A2<br />

has expired, the internal safety relay of the drive must have<br />

already dropped-out. Its checkback signal contacts AS 1/2<br />

indicate that the drive is in a safe condition.<br />

■ After the selected delay time has expired, the safely<br />

delayed enable contacts of the safety combination A2<br />

open.<br />

■ If the internal safety relay of the drive is functioning correctly,<br />

its checkback signal contacts AS1/2 are closed and<br />

the internal line contactor of the rectifier unit does not<br />

drop-out. If the internal safety relay does not function correctly,<br />

its checkback signal contacts AS1/2 are not closed,<br />

the internal line contactor of the rectifier unit drops-out<br />

and isolates the drive from the line supply (2nd shutdown<br />

path!).<br />

■ When button S1 ("Off") is pressed, contactor K3 is no longer<br />

energized and the drop-out delay of time relay K2a is simultaneously<br />

started. When contactor K3 drops-out, a 0 signal<br />

is entered at contact 65 (controller enable) of the drive. The<br />

drive is immediately braked down to 0 speed and the pulses<br />

are cancelled. The internal safety relay of the drive is no<br />

longer energized after the drop-out delay time of time relay<br />

K2a has expired. The protective doors can be opened.<br />

Functional Example No. MC-FE-I-002-V11-EN 415<br />