Function description<br />

A structure in compliance with EN 954-1 control Category 3<br />

and EN1037 can be implemented using one SIGUARD safety<br />

combination for the protective doors. The drive is shut down<br />

(stopped) according to stop function Category 1 according to<br />

EN 60204-1.<br />

■ <strong>Safety</strong> combination for protective door monitoring functions<br />

corresponds to Category 4 (instantaneous enable circuit)<br />

or Category 3 (delayed enable circuit).<br />

■ Circuit for protective door monitoring is monitored through<br />

2 channels in a cross-circuit proof fashion.<br />

Behavior when the protective doors are opened<br />

When the protective doors are opened, it is initiated that the<br />

drive is shut down according to stop Category 1 in compliance<br />

with EN 60204-1. It must be ensured that potentially hazardous<br />

motion must have come to a standstill before a person can<br />

reach the potentially hazardous area!<br />

■ A 0 signal is entered, via the enable contact of safety combination<br />

A1, at contact X101.X (OFF3) of the drive. The<br />

drive is immediately braked down to 0 speed and the pulses<br />

are cancelled. The delay time of safety combination A1 is<br />

simultaneously started and the drive must have come to a<br />

standstill before it expires.<br />

Powering-up and powering-down the drive<br />

The drive can be started or stopped when the protective doors<br />

are closed.<br />

■ When the internal safety relay and line contactor K1 are in<br />

the correct state, safety combination A1 is brought into an<br />

operational state.<br />

■ Line contactor K1 and the internal safety relay of the drive<br />

are energized.<br />

■ When pressing S2 ("On"), contactor K2 is energized and<br />

latches. A 1 signal is entered at contact X101.X (OFF3) of<br />

the drive and the drive starts.<br />

■ Switches S4 and S5 are positively opening position<br />

switches corresponding to EN 1088.<br />

■ The drive is shut down via the internal safety relay and the<br />

higher-level line contactor K1.<br />

■ On circuit of safety combination A1 monitors whether the<br />

line contactor K1, the internal safety relay of the drive, as<br />

well as contactor K2, have dropped-out after the protective<br />

doors have been opened. (This is necessary in the sense of<br />

control Category 3 in compliance with EN 954-1!).<br />

■ The safely delayed enable contacts of safety combination<br />

A1 open after the selected delay time has expired. This<br />

means that the internal safety relay of the drive (1st shutdown<br />

path!) and line contactor K1 (2nd shutdown path!)<br />

are no longer energized.<br />

■ If the internal safety relay functions incorrectly or if line<br />

contactor K1 has not dropped-out, then its checkback signal<br />

contacts X533.1/2 in the on circuit of the safety combination<br />

A1 are not closed. The safety combination cannot be<br />

switched-in.<br />

■ When button S1 ("Off") is pressed, contactor K2 is no longer<br />

energized and a 0 signal is entered at contact X101.X<br />

(OFF3) of the drive. The drive is immediately braked down<br />

to 0 speed and the pulses are cancelled. If the protective<br />

doors are opened, the safely delayed enable contacts of<br />

safety combination A1 open after the selected delay time<br />

has expired. This means that the internal safety relay of the<br />

drive (1st shutdown path!) and line contactor K1 (2nd<br />

shutdown path!) are no longer energized.<br />

Functional Example No. MC-FE-I-001-V11-EN 403<br />

Ex. No.<br />

1.4