Ex. No.<br />

10 FC "REINTEGRATION" (FC 3)<br />

The reintegration applies for<br />

■ the LS4 (network 1)<br />

■ the F-DO<br />

■ the F-DI<br />

For the F-DO a memory bit REINT is prepared. With a positive<br />

flank of REINT the F-DO will be reintegrated.<br />

Warning!<br />

In this example, the reintegration of passivated<br />

modules occurs automatically. Only use the automatic<br />

reintegration for your applications if it does<br />

not cause hazards.<br />

A passivation is indicated via LED "SF" lighting up on the module.<br />

The reintegration of an F module may take approx. one<br />

minute.<br />

316 Functional Example No. AS-FE-I-010-V11-EN<br />

Operating instructions<br />

Prerequisites:<br />

■ Hardware configuration of STEP 7 as well as the fail-safe<br />

and user program are located in the S7-CPU<br />

■ No objects are currently in the detection zone of the LS4<br />

■ Zone pair 1 has been set (via positioning switch)<br />

■ The PC adapter has not been connected<br />

■ LS4 has been parameterized<br />

■ Zone pair 1 is active<br />

No. Instruction Result/Note<br />

1 Press the acknowledgement<br />

button ACK (E 1.0)<br />

Necessary prior to the first start.<br />

2 Press the start button<br />

START (E 0.0)<br />

Indicator light goes ON<br />

3 Place an object into the OSSD bit of LS4 becomes "0"<br />

detection zone<br />

-> Indicator light goes OFF<br />

4 Press the acknowledgement Necessary in case of error (here:<br />

button ACK (E 1.0) detection zone interrupted)<br />

5 Press the START button<br />

(E 0.0)<br />

Indicator light goes ON<br />

6 Now use the position Zone pair 2 is now active.<br />

switches to switch from Switching must be performed<br />

zone pair 1 to zone pair 2: within the time parameterized<br />

FIELD_BIT0="0",<br />

FIELD_BIT1="1"<br />

within FB4, NW5.