Ex. No.<br />

1<br />

F-CALL (FC1)<br />

F-CALL (FC1) is the F runtime group and is called from the cyclic<br />

interrupt OB (OB 35). F-CALL calls the F-programe block<br />

(here: FC2).<br />

FC "COORDINATION" (FC2)<br />

For modularity reasons all further failsafe blocks are called<br />

from here.<br />

FB "ESTOP" (FB1, DB1)<br />

The emergency stop is implemented as follows:<br />

#ACK<br />

#N<br />

N<br />

#ESTP<br />

#EN_ESTP<br />

SR<br />

S<br />

R Q<br />

#COND1<br />

#ACTUATOR<br />

=<br />

The signal status of #COND1 is defined in the user program<br />

(see FC 10 or OB 35). #COND1="1" is the first condition for a<br />

start of the "machine" (#ACTUATOR="1"). The second condition<br />

is the acknowledgement required before the start. The<br />

flipflop is set with #ACK="1" (#EN_ESTP="1"). In the standard<br />

user program (FC 10) the static variable #EN_ESTP is read as<br />

bit of the instance DB of FB1 and ensures, that only after acknowledgment<br />

the COND bit (or COND1 in the safety program)<br />

is set there by the start signal.<br />

By pressing the emergency stop button #ESTP becomes ="0"<br />

which sets the flipflop of the output Q back to "0" (resetting<br />

has the priority at this flipflop procedure), which makes #AC-<br />

TUATOR also "0". ("machine" is switched off).<br />

FC "REINTEGRATION" (FC3)<br />

This FC ensures the reintegration of the passivated failsafe<br />

modules (F-DI and/or F-DO). For the F-DO a memory bit REINT<br />

is prepared. With a positive flank of REINT the F-DO will be reintegrated.<br />

A passivation is indicated at the failsafe module<br />

via LED. The reintegration of an F module may take approx.<br />

one minute.<br />

Note<br />

In this example, the reintegration of passivated<br />

modules occurs automatically. Use the automatic reintegration<br />

for your application only if it will not<br />

cause any hazards.<br />

178 Functional Example No. AS-FE-I-001-V10-EN<br />

&<br />

G_FB_XX_081<br />

Operating instructions<br />

The table below will help you during operation.<br />

No. Instruction Result/Note<br />

1 Press the acknowledgement<br />

push button<br />

ACK and release it.<br />

–<br />

2 Press the push button<br />

for START instruction<br />

and release it.<br />

3 Press the emergency<br />

stop push button.<br />

4 Unlock emergency<br />

stop push button.<br />

Indicator light goes on<br />

("machine" active).<br />

Indicator light goes off. The output of<br />

the failsafe digital output module is<br />

reset.<br />

Perform action 1.