Emergency Stop with monitored start Category 4<br />

acc. to EN 954-1 with ET200S <strong>Safety</strong> Motorstarter Solution Local<br />

Function<br />

Description of the functionality<br />

If people (in production technology) are close to machines,<br />

then they must be protected using the appropriate equipment.<br />

The Emergency Stop control device represents a widely<br />

established component that protects man, machine and environment<br />

against potential hazards. In this <strong>Safety</strong> Functional<br />

Example, the Emergency Stop control device is monitored using<br />

two positively-driven contacts using the PM-D-F1 safety<br />

module in accordance with Category 4 acc. to EN 954-1. If the<br />

Emergency Stop control device is pressed, the PM-D-F1 safety<br />

module shuts down the motor starter assigned to it and the<br />

supply contactor according to Stop Category 0 acc. to EN<br />

60204-1. In this particular example, a drive is stopped. Before<br />

restarting or acknowledging the Emergency Stop shutdown<br />

using the start button, it is checked as to whether the contacts<br />

of the Emergency Stop control device are closed and the motor<br />

starter has been shut down. This example only discusses<br />

the safety function. The motor starter is operationally<br />

switched using a standard PLC and is not considered any further<br />

here.<br />

Note<br />

Equipment, functional aspects and Design Guidelines<br />

for Emergency Stop control devices are provided in<br />

EN 418 (EN ISO 13850 being prepared).<br />

Advantages/customer benefits<br />

■ Pure hardware engineering without having to configure/program<br />

software for the safety-relevant technology<br />

■ Extensive Profibus diagnostics of the motor starter and the<br />

PM-D-F1 safety module.<br />

■ As a result of the lower time/costs involved with materials<br />

and wiring, the mounting space in the cabinet is reduced<br />

and therefore the overall dimensions of the plants/system.<br />

Functional Example No. CD-FE-I-026-V10-EN 55<br />

Ex. No.<br />