Behavior when Emergency Stop is issued<br />

Emergency Stop is initiated using button S3 ("Emergency<br />

Stop"). This initiates that the drive is shut down according to<br />

stop Category 1 in compliance with EN 60204-1.<br />

■ A 0 signal is entered, via the enable contact of safety combination<br />

A1, at contact X101.X (OFF3) of the drive. The<br />

drive is immediately braked down to 0 speed and the pulses<br />

are cancelled.<br />

■ If the drive is stationary (speed = 0), then PLC output DO2<br />

to the internal safety relay of the drive is reset. The internal<br />

safety relay of the drive drops-out and its checkback signal<br />

contacts X533.1/2 close (1st shutdown path!).<br />

Behavior when the protective doors are opened<br />

When the protective doors are opened, it is initiated that the<br />

drive is shut down according to stop Category 1 in compliance<br />

with EN 60204-1. It must be ensured that potentially hazardous<br />

motion must have come to a standstill before a person can<br />

reach the potentially hazardous area!<br />

■ A 0 signal is entered, via the enable contact of safety combination<br />

A2, at contact X101.X (OFF3) of the drive. The<br />

drive is immediately braked down to speed 0 and the pulses<br />

are cancelled. At the same time, the state of the safety<br />

combination is signaled to the control.<br />

■ Before the selected delay time of safety combination A2<br />

has expired, the internal safety relay of the drive must have<br />

already dropped-out. Its checkback signal contacts<br />

X533.1/2 indicate that the drive is in a safe condition.<br />

Powering-up and powering-down the drive<br />

The drive can be started when the protective doors are closed<br />

and Emergency Stop button S3 is released.<br />

■ When button S1 ("On") is pressed, safety combination A1 is<br />

brought into the operational state. <strong>Safety</strong> combination A2<br />

is again in an operational state. Line contactor K1 is energized.<br />

■ The internal safety relay is energized (PLC output DO2), a 1<br />

signal is entered (PLC output DO3) at contact X101.X<br />

(OFF3) of the drive. The drive restarts.<br />

■ Before the selected delay time of safety combination A1<br />

expires, the internal safety relay of the drive must have<br />

already dropped-out and its checkback signal contacts<br />

X533.1/2 indicate that the drive is in a safe condition.<br />

■ The safely delayed enable contacts of safety combination<br />

A1 open after the selected delay time has expired. This<br />

means that line contactor K1 is no longer energized and the<br />

drive is electrically isolated from the line supply.<br />

■ The checkback signal of line contactor K1 is monitored in<br />

the on circuit of safety combination A1. If the contactor<br />

does not drop-out due to an incorrect function, then the<br />

drive is prevented from restarting after an Emergency Stop.<br />

■ If the drive is stationary (speed = 0), then PLC output DO2<br />

to the internal safety relay of the drive is reset. The internal<br />

safety relay of the drive drops-out and its checkback signal<br />

contacts X533.1/2 close. (1st shutdown path!)<br />

■ The safely delayed enable contacts of safety combination<br />

A2 open after the selected delay time has expired. This<br />

delay time must be set so that the checkback signal of the<br />

internal safety relay already indicates that the drive is in a<br />

safe condition.<br />

■ If the delay time of the contactor combination A2 has been<br />

correctly set and the function of the internal drive safety<br />

relay is correct, line contactor does not drop-out. If the<br />

delay time has been set too short or the internal safety relay<br />

is not functioning correctly, line contactor K1 drops-out and<br />

isolates the drive from the line supply (2nd shutdown<br />

path!).<br />

■ When button S2 is pressed ("Off"), PLC output DO3 is reset<br />

and a 0 signal is entered at contact X101.X (OFF3) of the<br />

drive. The drive is immediately braked down to 0 speed and<br />

the pulses are cancelled. If the drive is stationary (speed =<br />

0), then the PLC output DO2 to the internal safety relay of<br />

the drive is reset. If the protective doors are opened, the<br />

safely delayed enable contacts of safety combination A2<br />

open after the selected delay time has expired (1st shutdown<br />

path!). If the internal safety relay of the drive has still<br />

not dropped-out as a result of an incorrect function or a<br />

fault (PLC), line contactor K1 drops-out and isolates the<br />

drive from the line supply (2nd shutdown path!).<br />

Functional Example No. MC-FE-I-001-V11-EN 407<br />