Parameters used<br />

Below, some characteristic parameters are shown which were<br />

used for this example (with the motor used).<br />

Parameter No. Parameter name Value to be set Note/Explanation<br />

P0700 Selection of command source 2 (connecting terminal plate) There different options of starting or stopping the<br />

motor using the MICROMASTER, e.g. via the keyboard<br />

on the OP. In this example, the commands<br />

for starting/stopping the motor come from the<br />

standard output module (2DO HF) of the ET 200S<br />

and are transferred to the terminal connecting<br />

plate of the MICROMASTER.<br />

P0701 Function of digital input 1 1 (ON/OFF1) The commands for starting/stopping are acquired<br />

by digital input 1 on the MICROMASTER. If "1": Motor<br />

starts (ON)<br />

If "0": Motor stops (OFF1)<br />

P0731 Function of digital output 1 52.C (motor holding brake<br />

(MHB) active)<br />

Motor holding brake active (see also P1215)<br />

P0971 Transfer data from RAM to EEPROM 1 Start RAM -> EEPROM All values are transferred from RAM to EEPROM.<br />

P1120 Startup time 6 Time value in seconds required by the motor to accelerate<br />

from stop to the highest motor frequency.<br />

P1121 Ramp-down time 6 Time value in seconds required by the motor for<br />

delaying the maximum motor frequency until<br />

stop.<br />

P1215 Holding break enable 1: Motor holding brake enabled By the value 52.C in P0731, a relay is switched<br />

at the points 1 and 2 to control the brake. The<br />

relay is located at the terminals 11 and 12 of the<br />

MICROMASTER.<br />

Note<br />

The parameters are stored in the<br />

"as_fe_i_008_v10_code_pstopcat.zip" file. The<br />

"STARTER" software by <strong>Siemens</strong> is required to use this<br />

file. Page 273 provides information on where to download<br />

this software.<br />

fmin<br />

(P1080)<br />

Point 1 Point 2<br />

Warning!<br />

Please note that the parameters stored in the file<br />

"as_fe_i_008_v10_code_pstopcat.zip" refer to the<br />

motor with holding break used by us for testing. If<br />

you use a different motor, the parameters have to be<br />

adapted for the MICROMASTER.<br />

For safety reasons, the motor with the prepared parameters<br />

does not accelerate to maximum speed.<br />

Functional Example No. AS-FE-I-008-V11-EN 265<br />