Ex. No.<br />

11 Scenario: Automatic reintegration<br />

Disconnecting an F-DI and the ESTP_ACTUATOR emergency<br />

stop button, a channel error, hence passivation, is triggered.<br />

The PASSIVATION_ON indicator light is switched on, the<br />

ACTUATOR indicator light is switched off. The F-DI is configured<br />

with "Passivate the entire module", which is why the entire<br />

F-DI is passivated. This is made clear by the fact that the<br />

TEST 1) indicator light is switched off.<br />

After restoring the connection, the module is automatically<br />

reintegrated, the TEST indicator light is switched on.<br />

Overview for hardware setup<br />

START_ACTUATOR<br />

Button (NO)<br />

PS<br />

307<br />

ACK_ESTP_ACTUATOR<br />

Button (NO)<br />

ACK_PASS_ACTUATOR<br />

Button (NO)<br />

CPU<br />

315F<br />

IM<br />

151 HF<br />

PM-E<br />

(1)<br />

1) TEST indicator light is controlled with "1" via the input of the<br />

F-DI. Due to passivation of the entire module, the safety program<br />

now reads "0" at the input instead of "1".<br />

330 Functional Example No. AS-FE-I-011-V10-EN<br />

After acknowledging the user via the ACK_ESTP_ACTUATOR<br />

button, the ACTUATOR indicator light can be switched on via<br />

the START_ACTUATOR button.<br />

4 DI 4 DO PM-E<br />

(2)<br />

Warning!<br />

Automatic reintegration is only permitted if an automatic<br />

startup of the plant is not possible after the error<br />

has been removed.<br />

Wire-break<br />

4/8 F-DI 4 F-DO<br />

REQ_ACK_PASS_ACTUATOR PASSIVATION_ON REQ_ACK_ESTP_ACTUATOR<br />

Light (white) Light (green) Light (white)<br />

Meaning of background colors:<br />

Green: Buttons and indicator lights for normal operation<br />

Orange: Buttons and indicator lights for demonstration of passivation and reintegration<br />

x<br />

TEST<br />

Light (yellow)<br />

ACTUATOR<br />

Light (yellow)<br />

ESTP_ACTUATOR<br />

Switch (NC/NC)