19.08.2013 Views

Safety Integrated - Industry - Siemens

Safety Integrated - Industry - Siemens

Safety Integrated - Industry - Siemens

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

SIMOCODE pro direct starters with safety technology<br />

Emergency stop monitoring with monitored start<br />

Category 4 according to EN 954-1<br />

Function<br />

Description of the Functionality<br />

Persons near machines (e.g. in production engineering) must<br />

be suitably protected by technical equipment. The<br />

EMERGENCY STOP control unit is a widely used component for<br />

protecting persons, machines and the environment against<br />

danger.<br />

SIMOCODE pro is a flexible, modular motor management system<br />

for low-voltage motors with constant speeds. It optimizes<br />

the connection between I&C and the motor feeder, increases<br />

plant availability while helping to cut planning and commissioning<br />

costs during plant operation and maintenance. <strong>Integrated</strong><br />

in the low-voltage switchgear, SIMOCODE pro is the intelligent<br />

connection between the higher-level automation<br />

system and the motor feeder.<br />

In this <strong>Safety</strong> Functional Example, the EMERGENCY STOP control<br />

unit with positive opening contacts is monitored by a<br />

SIRIUS 3TK2823 safety switching device as per category 4 according<br />

to EN 954-1. If the EMERGENCY STOP is activated, the<br />

3TK2823 safety switching device switches off its corresponding<br />

drive as per Stop Category 0 according to EN 60204-1.<br />

Activation of the EMERGENCY STOP is signaled to the<br />

SIMOCODE pro via the IN4 input. This signal is used to activate<br />

the switching state in SIMOCODE when the EMERGENCY STOP<br />

is activated. If this contact reports "zero", SIMOCODE issues<br />

the OFF command. After the EMERGENCY STOP has been released<br />

and the safety switching device has been acknowledged,<br />

the signal at the IN4 input is active and the drive can<br />

be restarted.<br />

A yellow LED on the operator panel will light up if the<br />

3TK2823 trips. The operator can start the drive again as soon<br />

as the LED turns off.<br />

The same signal is sent to the higher-level PLC via the Cyclic<br />

Send 1 function, and can be used here to release the switchon<br />

function in the remote operating mode.<br />

This example takes the safety function into particular consideration.<br />

Operational switching of the motor feeder is via a<br />

standard PLC and is not taken into further consideration here.<br />

Note<br />

Equipment, functional aspects and design guidelines<br />

for EMERGENCY STOP control units can be found in<br />

EN 418 (ISO 73850).<br />

Flow Diagram<br />

The following flow diagram illustrates functional interrelationships<br />

(for reasons of clarity, operational stopping has not been<br />

included)<br />

Start<br />

Operating voltage<br />

switched on?<br />

yes<br />

Has the<br />

EMERGENCY STOP<br />

pushbutton been released?<br />

yes<br />

acknowledged?<br />

yes<br />

EMERGENCY STOP<br />

is acknowledged,<br />

K1 is activated<br />

EMERGENCY STOP<br />

signal to<br />

SIMOCODE pro<br />

changes to 1,<br />

SIMOCODE pro<br />

is ready for switch-on<br />

Start command?<br />

yes<br />

SIMOCODE pro<br />

starts the motor,<br />

K2 is activated<br />

Drive is running<br />

no<br />

no<br />

no<br />

no<br />

Is the motor running?<br />

Has the<br />

EMERGENCY STOP<br />

pushbutton been pressed?<br />

Functional Example No. CD-FE-I-037-V10-EN 127<br />

no<br />

yes<br />

3TK2823 switches off<br />

K 1 and K 2<br />

Drive stops and is<br />

disconnected from<br />

the network<br />

EMERGENCY STOP<br />

signal to SIMOCODE<br />

pro changes activates<br />

the switch-off command<br />

SIMOCODE pro signals<br />

EMERGENCY STOP<br />

on the operator panel<br />

and sends the message<br />

via cycl. signal data<br />

yes<br />

no<br />

Stop category 0<br />

Ex. No.<br />

5.1

Hooray! Your file is uploaded and ready to be published.