Network 2<br />

With OUT3=0 the drive is brought to standstill with fast stop.<br />

The subsequent safe shutdown becomes active with a time<br />

delay (see figure below). Without time delay, the pulse blocking<br />

(Option K80) would be active immediately so that a fast<br />

stop (with OUT3) would not be possible any more.<br />

NERR_ESTP_FDOR receives the state of the SR flip-flop from<br />

NW1, which sets or resets OUT3. If OUT3 is reset, DELAY_80 is<br />

also reset after the time parameterized at PT has elapsed.<br />

Network 3<br />

FB F_FDBACK (FB216) is a certified block from the Distributed<br />

<strong>Safety</strong> block library.<br />

Note<br />

Further information on the FB216 is available for example<br />

by selecting it in the block editor and pressing<br />

F1.<br />

Network 4<br />

FB F_FDBACK (FB216) is a certified block from the Distributed<br />

<strong>Safety</strong> block library.<br />

FC "REINT" (FC 10)<br />

The FC 10 causes the reintegration of F-DI and F-DO, in order<br />

to depassivate them. This requires that:<br />

■ the error that caused the passivation has been removed<br />

and<br />

■ a positive edge has been set at the parameter ACK_REI of<br />

the respective F-Periphery DB.<br />

A passivation is indicated by an illuminated LED "SF" on the<br />

module. The reintegration of an F module may take several<br />

minutes.<br />

Functional Example No. AS-FE-I-012-V10-EN 393<br />

Ex. No.<br />

12