Ex. No.<br />

5.1<br />

■ (1.) Also for this module, safety-relevant operation must be<br />

enabled by selecting <strong>Safety</strong> mode as the operating mode.<br />

■ (2.) The binary code that is specified under DIL switch setting<br />

(9......0) must be set at the rear of the module.<br />

DIL switch on the module:<br />

■ (3.) The short-circuit and cross-circuit fault monitoring of<br />

the channel group is activated by selecting the function<br />

Sensor supply via module .<br />

■ (4.) The properties of the individual channels of the<br />

module are parameterized as shown under channel 0, 12.<br />

For more detailed information please refer to the Manual<br />

SIMATIC Automation System S7-300 Fail-Safe Signal<br />

Modules.<br />

■ "In order that the SINAMICS G120 safety functions can be<br />

used in the safety program, symbolic addresses must be<br />

assigned to the inputs of the safety input module. The<br />

input window for the symbolic addresses is opened by<br />

480 Functional Example No. SD-FE-I-001-V11-EN<br />

selecting the module, pressing the righthand mouse key<br />

and selecting Edit Symbols...<br />

Properties of the SINAMICS G120<br />

The window of the SINAMICS G120 PROFIBUS properties (2) is<br />

displayed by clicking once on the SINAMICS G120 icon (1).<br />

The PROFIBUS telegram (2.) between the CPU and the<br />

SINAMICS G120 comprises two components. On one hand the<br />

PROFIsafe module for the safety functions - that must be first<br />

entered - and the <strong>Siemens</strong> telegram to control the SINAMICS<br />

G120 (control signals, status word, frequency set-point, frequency<br />

actual value etc.).