Ex. No.<br />

11 What type of passivation exists?<br />

The following table gives an overview of the passivation:<br />

Cause of the passivation Effect of the passivation Reaction in the<br />

F-I/O-module data<br />

block<br />

<strong>Safety</strong> program Setting "PASS_ON = 1" in the F-I/O-module<br />

data block<br />

F-operating system<br />

Startup of the F-CPU<br />

Establishing communication between the F-<br />

CPU and the F-I/O via the safety protocol according<br />

to PROFIsafe.<br />

F-communication error<br />

Error at fail-safe communication between F-<br />

CPU and F-I/O.<br />

F-I/O error<br />

(*1)<br />

Module error<br />

• Configuration error<br />

• Overtemperature<br />

Channel error<br />

• Wire break<br />

• Short circuit<br />

• Discrepancy<br />

• Overload<br />

Explanations on the table:<br />

(*1): "F-I/O faults" causes the following reaction:<br />

■ The error is reported at the F-CPU (as standard reaction):<br />

- The error is reported to the F-CPU via the slave diagnostics.<br />

- OB82 for I/O errors is called in the F-CPU. If it does not<br />

exist, it goes to the F-CPU in STOP.<br />

■ Either the entire F-module or only the affected channels<br />

are passivated (F-specific reaction).<br />

(*2): In the hardware configuration of STEP 7 the project settings<br />

can be selected: "Passivate the entire module" or "Passivate<br />

the channels".<br />

354 Functional Example No. AS-FE-I-011-V10-EN<br />

.<br />

Passivation of the F-module QBAD = 1<br />

All channels:<br />

QBAD_I_xx = 1<br />

QBAD_O_xx = 1<br />

Passivation of the entire F-I/O QBAD = 1<br />

PASS_OUT = 1<br />

All channels:<br />

QBAD_I_xx = 1<br />

Passivation of the F-module<br />

QBAD_O_xx = 1<br />

Passivation of the F-module<br />

Configuration:<br />

(*2)<br />

"Passivation of entire<br />

module"<br />

"Passivation channel" QBAD = 1<br />

PASS_OUT = 1<br />

Only affected channel:<br />

QBAD_I_xx = 1<br />

QBAD_O_xx = 1