Ex. No. Protective door monitoring with automatic start Category 2<br />

3.3<br />

acc. to EN 954-1 with ET200S <strong>Safety</strong> Motorstarter Solution Local<br />

Function<br />

Description of the functionality<br />

This <strong>Safety</strong> Functional Example describes a mechanically isolating<br />

protective mechanism in the form of a protective door.<br />

The most frequently used solution for plants and machines to<br />

secure hazardous areas is mechanically isolating protective<br />

equipment or access hatches. In this case, the function is to<br />

monitor unauthorized entry into plant and system areas as<br />

well as to prevent potentially hazardous machine functions if<br />

the protective equipment - in this case protective door - is not<br />

closed.<br />

The protective door is monitored by a SIRIUS position switch<br />

with positively-opening contacts using a PM-D-F2 safety module<br />

according to Category 2 in compliance with EN 954-1. If<br />

this protective door is opened, the PM-D-F2 safety module<br />

shuts down the motor starter assigned to it according to Stop<br />

Category 0 acc. to EN 60204-1. In this particular example, a<br />

drive is stopped. If the protective door is closed, after the position<br />

switch is checked, the motor automatically starts.<br />

This example only discusses the safety function. The motor<br />

starter is operationally switched using a standard PLC and is<br />

not considered any further here.<br />

Advantages/customer benefits<br />

■ Pure hardware engineering without having to configure/program<br />

software for the safety-relevant technology<br />

■ Extensive Profibus diagnostics of the motor starter and the<br />

PM-D-F2 safety module.<br />

■ As a result of the lower time/costs involved with materials<br />

and wiring, the mounting space in the cabinet is reduced<br />

and therefore the overall dimensions of the plants/system.<br />

Contactor contacts welded signal<br />

Using this circuit example, Category 2 according to EN 954-1<br />

can only be fulfilled if, when the actuator fails, an alarm is automatically<br />

output or the machine control initiates a safe condition.<br />

If this is not the case, a second shutdown path is required.<br />

This signal can be generated using the process image of the<br />

motor starter.<br />

58 Functional Example No. CD-FE-I-027-V10-EN<br />

ET200S Standard ET200S HF<br />

PAE 0.0 Ready 0.0 Ready (automatic)<br />

0.1 Close contactor 0.1 Start motor (current<br />

measurement)<br />

0.2 Circuit-breaker 0.2 Group fault<br />

tripped<br />

0.3 Group alarm<br />

0.4 Input 1<br />

0.5 Input 2<br />

0.6 Input 3<br />

0.7 Input 4<br />

1.0-1.5 Motor current Iact 1.6 Mode H-V-O<br />

1.7 Ramp mode (only<br />

DSS1e-x)<br />

PAA 0.0 Motor clockwise 0.0 Motor clockwise<br />

0.1 Motor counter-clockwise<br />

0.2 Brake 0.2 Release brake<br />

0.3 Trip reset<br />

0.4 Emergency start<br />

0.5 Self-test<br />

Netzwork 1:Time delay of the protective door signal<br />

Comments:<br />

#Protective door<br />

T1<br />

& SE<br />

Network 2:Feedback signal, contactor contacts welded, standard motor starter<br />

Comments:<br />

#Contactor_closed<br />

T1<br />

S5T#500MS<br />

&<br />

#Contactor_welded<br />

&<br />

Typical block: Signal, contactor contacts welded for motor starter<br />

standard<br />

Using the standard output "contactor welded" an indicator<br />

light can be controlled. As a result of this signal, a second<br />

shutdown path is no longer required.<br />

Note<br />

The position switches must be arranged so that they are<br />

not damaged when they are approached and passed.<br />

This is the reason that they may not be used as mechanical<br />

endstop.<br />

TW<br />

G_FB_XX_069