Description: FB3, DB4 (REINTEGRATION)<br />

Function of the F-block:<br />

■ Display of passivation at the PASSIVATION_ON indicator<br />

light<br />

■ Automatic reintegration of the F-DI<br />

■ Manual reintegration of F-DI/F-DO<br />

Parameter of the F-block:<br />

■ None<br />

FB3 / Network 1<br />

F-DO<br />

DB820.DBX 8.0<br />

DB820.DBX 8.1<br />

F-DI<br />

DB819.DBX 2.1<br />

Overview of the signals of the network:<br />

Signal Source / Target Meaning<br />

F00007_4_F_DO_DC24V_2A.QBAD_O_00 From F-I/O-module data block of F-DO If "1": channel F-DO is passivated<br />

F00007_4_F_DO_DC24V_2A.QBAD_O_01 If "1": channel 1 of F-DO is passivated<br />

F00001_4_8_F_DI_DC24V.QBAD From F-I/O-module data block of F-DI If "1": At least one channel of the F-DI is passivated.<br />

PASSIVATION_ON To process (indicator light) If "1": At least one channel of F-DI and/or<br />

F-DO is passivated.<br />

Functional Example No. AS-FE-I-011-V10-EN 339<br />