Ex. No.<br />

11<br />

"Protection" tab:<br />

Mode used here is "Test Mode":<br />

The Mode field is not relevant for safety operation.<br />

Settings of the F-DI<br />

You reach the input dialog in the HW configuration of STEP 7<br />

by double-clicking "4/8 F-DI DC24V" (see Figure „Overview of<br />

the configuration“).<br />

All input screens are available in the "Parameter" tab.<br />

"DIP switch setting (9…0)":<br />

The displayed value must be set at the F-DI.<br />

"F-monitoring time (ms)":<br />

"150 ms"<br />

Important: The F-monitoring time must be larger than the call<br />

time of OB35. Please use the Cotia table for selecting the monitoring<br />

time ("min. F-monitoring time" sheet). At page 326 you<br />

find the link to the Cotia table.<br />

324 Functional Example No. AS-FE-I-011-V10-EN<br />

"Short-circuit test":<br />

"cyclic"<br />

The two channel emergency stop button contains the power<br />

supply via the module.<br />

"Behavior after channel faults":<br />

"Passivate the entire module"<br />

"Channel 0.4":<br />

"activate"<br />

The two break contacts of the emergency stop push button<br />

are polled with a 1oo2 evaluation.<br />

"Channel 1.5":<br />

"activate"<br />

"1" is read at channel 1. This directly controls the TEST indicator<br />

light.<br />

Unused channels:<br />

"deactivate"<br />

"Channel 0.4":<br />

"Evaluation of the sensors":<br />

"1oo2 evaluation"<br />

"Type of sensor interconnection":<br />

"2 channel equivalent"<br />

"Behavior of discrepancy":<br />

"0-Supply value"<br />

"Discrepancy time (ms)":<br />

"10 ms"