Behavior when Emergency Stop is issued<br />

Emergency Stop is initiated using button S3 ("Emergency<br />

Stop"). This initiates that the drive is shut down according to<br />

stop Category 1 in compliance with EN 60204-1.<br />

■ A 0 signal is entered at contact 65 (controller enable) of the<br />

drive via the enable contacts of safety combination A1. The<br />

drive is immediately braked down to 0 speed and the pulses<br />

are cancelled.<br />

■ If the drive is stationary (speed = 0), then PLC output DO2<br />

to the internal safety relay of the drive is reset. The internal<br />

safety relay of the drive drops-out and its checkback signal<br />

contacts AS1/2 close (1st shutdown path!).<br />

Behavior when the protective doors are opened<br />

When the protective doors are opened, it is initiated that the<br />

drive is shut down according to stop Category 1 in compliance<br />

with EN 60204-1. It must be ensured that potentially hazardous<br />

motion must have come to a standstill before a person can<br />

reach the potentially hazardous area!<br />

■ A 0 signal is entered at contact 65 (controller enable) of the<br />

drive via the enable contacts of safety combination A2. The<br />

drive is immediately braked down to 0 speed and the pulses<br />

are cancelled. At the same time, the state of the safety<br />

combination is signaled to the control.<br />

■ Before the selected delay time of safety combination A2<br />

expires, the internal safety relay of the drive must have<br />

already dropped-out and its checkback signal contacts<br />

AS1/2 indicate that the drive is in a safe condition.<br />

Powering-up and powering-down the drive<br />

The drive can be started when the protective doors are closed<br />

and Emergency Stop button S3 is released.<br />

■ When pressing button S2 ("On"), safety combination A1 is<br />

brought into the operational state. <strong>Safety</strong> combination A2<br />

is again in an operational state. The internal line contactor<br />

of the rectifier unit is energized.<br />

■ The internal safety relay is energized (PLC output DO2), a 1<br />

signal is entered (PLC output DO3) at contact 65 (controller<br />

enable) of the drive. The drive restarts.<br />

■ Before the selected delay time of safety combination A1<br />

expires, the internal safety relay of the drive must have<br />

already dropped-out and its checkback signal contacts AS<br />

1/2 indicate that the drive is in a safe condition.<br />

■ The safely delayed enable contacts of safety combination<br />

A1 open after the selected delay time has expired. This<br />

means that the internal line contactor of the rectifier unit is<br />

no longer energized and the drive is electrically isolated<br />

from the line supply.<br />

■ The checkback signal of the internal line contactor of the<br />

rectifier unit is monitored. If the contactor does not dropout<br />

due to an incorrect function, then the drive is prevented<br />

from restarting after an Emergency Stop.<br />

■ If the drive is stationary (speed = 0), then PLC output DO2<br />

to the internal safety relay of the drive is reset. The internal<br />

safety relay of the drive drops-out and its checkback signal<br />

contacts close (1st shutdown path!)<br />

■ The safely delayed enable contacts of safety combination<br />

A2 open after the selected delay time has expired. This<br />

delay time must be set so that the checkback signal of the<br />

internal safety relay already indicates that the drive is in a<br />

safe condition.<br />

■ If the delay time of the contactor combination A2 has been<br />

correctly set and the function of the internal drive safety<br />

relay is correct, the internal line contactor of the rectifier<br />

unit does not drop-out. If the delay time is set too short or<br />

if the internal safety relay does not function correctly, the<br />

internal line contactor of the rectifier unit drops-out and<br />

isolates the drive from the line supply (2nd shutdown<br />

path!).<br />

■ When button S2 is pressed ("Off"), PLC output DO3 is reset<br />

and a 0 signal is entered at contact 65 (controller enable)<br />

of the drive. The drive is immediately braked down to 0<br />

speed and the pulses are cancelled. If the drive is stationary<br />

(speed = 0), then the PLC output DO2 to the internal safety<br />

relay of the drive is reset. If the protective doors are<br />

opened, the safely delayed enable contacts of safety combination<br />

A2 open after the selected delay time has expired<br />

(1st shutdown path!). If the internal safety relay of the<br />

drive has still not dropped-out as a result of an incorrect<br />

function or a fault (PLC), the internal line contactor of the<br />

rectifier unit drops-out and isolates the drive from the line<br />

supply (2nd shutdown path!).<br />

Functional Example No. MC-FE-I-002-V11-EN 423<br />

Ex. No.<br />

2.6