Scenario: F-communication error<br />

Disconnecting the F-CPU and the decentralized station (unplugging<br />

the PROFIBUS DP cable) causes passivation of the entire<br />

F-I/O-modules in the distributed station.<br />

After restoring the connection (plugging the PROFIBUS DP<br />

cable back in) the F-I/O-modules remain passivated. The<br />

switched on PASSIVATION_ON indicator light indicates this.<br />

If the user acknowledges via ACK_PASS_ACTUATOR, the F-I/O<br />

is reintegrated.<br />

Overview for hardware setup<br />

Disconnect cable<br />

START_ACTUATOR<br />

Button (NO)<br />

PS<br />

307<br />

ACK_ESTP_ACTUATOR<br />

Button (NO)<br />

ACK_PASS_ACTUATOR<br />

Button (NO)<br />

CPU<br />

315F<br />

x<br />

IM<br />

151 HF<br />

Power Supply by PM-E (1) Power Supply by PM-E (2)<br />

PM-E<br />

(1)<br />

4 DI 4 DO PM-E<br />

(2)<br />

4/8 F-DI 4 F-DO<br />

REQ_ACK_PASS_ACTUATOR PASSIVATION_ON REQ_ACK_ESTP_ACTUATOR<br />

Light (white) Light (green) Light (white)<br />

Meaning of background colors:<br />

Green: Buttons and indicator lights for normal operation<br />

Orange: Buttons and indicator lights for demonstration of passivation and reintegration<br />

TEST<br />

Light (yellow)<br />

ACTUATOR<br />

Light (yellow)<br />

ESTP_ACTUATOR<br />

Switch (NC/NC)<br />

Functional Example No. AS-FE-I-011-V10-EN 331<br />

Ex. No.<br />

11