The displayed link is parameterized in the SIMOCODE ES Professional<br />

software graphic editor to activate the EMERGENCY<br />

STOP function.<br />

A truth table is switched between the "OFF" socket of the control<br />

station and the "OFF" plug of the "protecting/controlling"<br />

function. The "EMERGENCY STOP" signal from BU input 4 is assigned<br />

to the "E3" plug of the truth table. The truth table wiring<br />

is illustrated as follows.<br />

The "Cyclic Send 1" function is used to signal the EMERGENCY<br />

STOP to the higher-level PLC. In this case, the "EMERGENCY<br />

STOP" signal from the BU input is assigned to Bit 0. The yellow<br />

3 LED is used to visually indicate the EMERGENCY STOP on the<br />

operator panel (see the figure on page 138).<br />

SIMOCODE issues a warning via the External Fault 1 function<br />

whenever the EMERGENCY STOP is activated.<br />

Functional Example No. CD-FE-I-037-V10-EN 139<br />

Ex. No.<br />

5.1