Ex. No.<br />

11 The following table gives an overview of the reintegration.<br />

Cause of the passivation: Reintegration<br />

Manual or automatic Prerequisite for reintegration<br />

<strong>Safety</strong> program Setting "PASS_ON = 1" in the F-I/O-module data<br />

block<br />

automatic "PASS_ON = 0"<br />

F-operating system Startup of the F-CPU<br />

Startup of the F-CPU<br />

Establishing communication between the F-CPU<br />

and the F-I/O via the safety protocol according to<br />

PROFIsafe.<br />

automatic Communication established<br />

F-communication error<br />

Error at fail-safe communication between F-CPU<br />

and F-I/O.<br />

F-I/O error Module error<br />

• Configuration error<br />

• Overtemperature<br />

Channel error<br />

• Wire break<br />

• Short circuit<br />

• Discrepancy<br />

• Overload<br />

Explanations on the table:<br />

(*1):<br />

After removing the error, the SF-LED of the affected F-module<br />

and the S7-message system does not indicate an error anymore.<br />

The passivation of the F-module remains until reintegration<br />

(see page 358 and 359).<br />

356 Functional Example No. AS-FE-I-011-V10-EN<br />

manual F-system has recognized<br />

that the error causing the<br />

passivation has been re-<br />

Depending on ACK_NEC:<br />

• If "0":<br />

automatic<br />

• "If "1":<br />

manual<br />

(Default value)<br />

moved. (*1)