Ex. No.<br />

10 Configuration software/tools<br />

Component Type MRPD / Ordering data Qty Manufacturer<br />

SIMATIC STEP 7 V5.3 + SP1 6ES7810-4CC07-0YA5 1 <strong>Siemens</strong> AG<br />

SIMATIC Distributed <strong>Safety</strong> V5.3 6ES7833-1FC01-0YA5 1<br />

LS4Soft V1.08 Delivered with the LS4 1<br />

Setup and Wiring<br />

Overview of the hardware configuration<br />

Like the ET 200S, the laser scanner LS4-4 is operated at<br />

PROFIBUS DP as a DP slave. A fail-safe S7-CPU is thereby used as<br />

DP master.<br />

PS<br />

307<br />

Laser scanner<br />

LS4-4<br />

CPU<br />

315F<br />

DP<br />

Button for<br />

restarting the<br />

LS4-4 (NO)<br />

PM-E 2DI<br />

HF<br />

F-DI<br />

IM 151<br />

HF<br />

2DI<br />

HF<br />

PM-E F-DO<br />

4DI HF<br />

START<br />

STOP<br />

ACK<br />

Indicator light<br />

Position button for<br />

zone pair switching<br />

(NC)<br />

Warning!<br />

In this example, the actuator is simulated by an indicator<br />

light. For reaching safety category 3, the actuator must<br />

be read back via two channels (using two contactors).<br />

Note<br />

One 4DI electronic module can be used instead of both<br />

2DI electronic modules. The "high feature" electronic<br />

modules can also be replaced by standard modules.<br />

298 Functional Example No. AS-FE-I-010-V11-EN<br />

Wiring of the hardware components<br />

Requirements: The power supplies are supplied with 230V AC.<br />

First check the addresses set at the hardware components<br />

listed below:<br />

Hardware<br />

component<br />

IM 151 High<br />

Feature<br />

Laserscanner<br />

LS4-4<br />

Address<br />

to be set<br />

6 (PROFIBUS<br />

address)<br />

4 (PROFIBUS<br />

address)<br />

F-DI Switch position:<br />

1111111110<br />

F-DO Switch position:<br />

1111111101<br />

Note<br />

Can be changed<br />

Default setting, can be<br />

changed<br />

The PROFIsafe addresses are<br />

automatically assigned during<br />

configuring the fail-safe<br />

modules in STEP 7. The<br />

PROFIsafe addresses 1 to<br />

1022 are permissible. Please<br />

make sure that the setting at<br />

the address switch (DIL<br />

switch) on the side of the<br />

module corresponds to the<br />

PROFIsafe address in the<br />

hardware configuration of<br />

STEP 7.<br />

Note<br />

The laser is not illustrated in the figure below. Its connections<br />

are discussed separately later on.<br />

Note<br />

The DP interface of the CPU 315F must be connected with<br />

the respective DP interface of the IM 151 HF.<br />

Note<br />

The wiring of the hardware is illustrated below. In the<br />

following table, the hardware components occurring<br />

several times are numbered so they can be allocated in<br />

the subsequent wiring plan.