Ex. No.<br />

1<br />

Testing inputs and outputs<br />

Requirements: The inputs and outputs have the default values<br />

specified under "Inputs/outputs used".<br />

No. Instruction Response<br />

A24.0<br />

Note<br />

1 None "0" After start of the S7-CPU<br />

2 Press ACK and release<br />

the button<br />

"0" Acknowledgement<br />

3 Press START and "1" "Machine" (here simulated by<br />

release the button<br />

indicator light) runs<br />

4 Press ESTP "0" Emergency stop pressed<br />

174 Functional Example No. AS-FE-I-001-V10-EN<br />

Important hardware component settings<br />

Below, several important settings from the hardware configuration<br />

of STEP 7 are shown to provide you with an overview.<br />

These settings are available in the included STEP 7 project. It<br />

is basically possible to change these settings (e.g. due to individual<br />

requirements), but please consider the following note:<br />

Warning!<br />

The settings shown below contribute to meet the requirements<br />

of <strong>Safety</strong> Category 4. Changes at the settings<br />

may cause loss of the safety function.<br />

If you implement changes (e.g. add an additional module),<br />

the sample code has to be adapted accordingly.<br />

The safety protector is not listed in the hardware configuration<br />

of STEP 7.<br />

Overview picture<br />

The PROFIBUS adress at IM 153-2 is set using DIP-switches.