Ex. No.<br />

12 Flowchart<br />

The flowchart below illustrates the functional relations.<br />

"Check of plausibility OK?" in the flowchart involves:<br />

■ checking whether the actual speed value does not exceed<br />

a fixed speed value N_MAX.<br />

■ checking whether the actual speed value determined with<br />

PROFIBUS and the actual speed value determined with the<br />

ET 200S count module are equal.<br />

If both points can be answered with "YES", then the plausibility<br />

check is "OK". For "NO" and "safe speed" mode, the drive is<br />

switched off safely.<br />

Time sequence for different modes<br />

The following time diagrams show the time sequence during:<br />

■ Operational start and shutdown of the drive<br />

■ Emergency stop<br />

■ Operating mode "safe speed" (SG)<br />

Before, the displayed parameters are explained. The names of<br />

the signals correspond to the ones of the S7 program code.<br />

368 Functional Example No. AS-FE-I-012-V10-EN<br />

Symbol Function Convention<br />

ACK Acknowledgement Acknowledgement depending<br />

on edge evaluation<br />

START Start request 1: Start request<br />

STOP Stop request 0: Stop request<br />

ESTP Emergency Stop 0: Activated emergency<br />

stop<br />

SIM_FDOR Simulated safety door 0: Opened safety door<br />

DMS Dead man switch 1: DMS pressed<br />

OUT3 Parameter<br />

MASTERDRIVES<br />

0: Fast stop<br />

K80 Contactor for control- 1: <strong>Safety</strong> relay of K80<br />

ling the option K80 option is controlled<br />

K2 Line contactor 1: activated<br />

n Speed list value<br />

Operational start and shutdown of the drive<br />

Time Explanation<br />

t1 Acknowledgement required prior to first start obligatory.<br />

t2 Drive is started via START.<br />

t3 Drive is stopped via STOP.<br />

t4 Drive standstill