Ex. No.<br />

9 Function test<br />

The inputs and outputs used can be checked with regard to<br />

their functionality, if<br />

■ the hardware components are wired<br />

■ the S7 project was loaded to the F CPU<br />

Inputs/outputs used<br />

No. Hardware<br />

component<br />

Testing inputs and outputs<br />

Requirements: The inputs and outputs have the default values<br />

specified under "Inputs/outputs used".<br />

Note<br />

After an emergency stop (and when starting for the first<br />

time), an acknowledgement is required before a restart.<br />

284 Functional Example No. AS-FE-I-009-V10-EN<br />

Adress Symbol Signal<br />

(default value)<br />

1 Emergency stop push button (NC / NC) E 0.0 ESTP1 "1" Emergency stop for group 1<br />

2 Emergency stop push button (NC / NC) E 0.1 ESTP2 "1" Emergency stop for group 2<br />

3 Emergency stop push button (NC / NC) E 0.2 ESTP_ALL "1" Emergency stop for all groups<br />

4 Push button (NO) E 6.0 START_M1 "0" Start requirement group 1<br />

5 Push button (NO) E 6.1 ACK_M1 "0" Acknowledgement for group 1<br />

6 Contactor auxiliary contact (NC) E 7.0 K12_HELP "1" Readback signal (group 1)<br />

7 Push button (NO) E 7.1 START_M2 "0" Start requirement group 2<br />

8 Push button (NO) E 8.0 ACK_M2 "0" Acknowledgement for group 2<br />

9 Contactor auxiliary contact (NC) E 8.1 K34_HELP "1" Readback signal (group 2)<br />

10 Push button (NO) E 9.0 ACK_ALL "0" Acknowledgement signal for<br />

groups 1 and 2<br />

11 Magnet coil contactor A16.0 M1 "0" For motor M1 (group 1, connection<br />

to F-DO)<br />

12 Magnet coil contactor A16.1 M2 "0" For motor M2 (group 2, connection<br />

to F-DO)<br />

Note<br />

Note<br />

You can also test the instructions listed in the table below<br />

without connected main circuit.<br />

No. Instruction M1 M2 Note<br />

1 Press the push button E 9.0 and release it. "0" "0" Acknowledgement required prior to first start. Instead of<br />

E 10.0, you can also press the two push buttons E 6.1<br />

and E 8.0.<br />

2 Press the push button E 6.0 and release it. "1" "0" Start request for motor M1.<br />

3 Press the push button E 7.1 and release it. "1" "1" Start request for motor M2.<br />

4 Press the emergency stop push button E 0.0 "0" "1" Single shutdown group 1<br />

5 Press the emergency stop push button E 0.1 "0" "0" Single shutdown group 2<br />

6 Unlock the pressed emergency stop buttons. "0" "0" –<br />

7 Repeat no. 1 to 3 "1" "1" Start request for motor M1 and M2.<br />

8 Press the emergency stop push button E 0.2 "0" "0" Group shutdown