19.08.2013 Views

Safety Integrated - Industry - Siemens

Safety Integrated - Industry - Siemens

Safety Integrated - Industry - Siemens

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Emergency stop<br />

Time Explanation<br />

t1 Acknowledgement required prior to first start obligatory<br />

t2 Drive is started via START.<br />

t3 Activates emergency stop: fast stop is triggered<br />

(OUT3=0).<br />

t4 Option K80: pulse blocking<br />

t5 Separating drive from network (only for readback error<br />

of option K80).<br />

t6 Unlocking the emergency stop button.<br />

t7 Negative edge of acknowledgement signal: Activates the<br />

contactor. OUT3 is reset to 1 signal. This is the prerequisite<br />

for the drive to be restarted with OUT1=1 (not depicted).<br />

Note<br />

The above time curve for OUT3, K80, K2 and n would<br />

also result if instead of triggering an emergency stop<br />

at t3, the safety door (simulated here) would be<br />

opened.<br />

Note<br />

The drive is only separated from the network, if the<br />

feedback contact of option K80 causes an error (see<br />

time value t5).<br />

Functional Example No. AS-FE-I-012-V10-EN 369<br />

Ex. No.<br />

12