Ex. No.<br />

5.1<br />

Important hardware component settings<br />

Most of the module/board settings are made in the HW Config<br />

in the software. Hardware settings are only required for the<br />

following modules/boards.<br />

The modules/boards must be set with the control system in a<br />

no-voltage state.<br />

SM374 simulation module<br />

This module can be operated as 16 x DO (output via LED),<br />

16 x DI (input via switch) or as combined 8 x DI / 8 x DO.<br />

The last combination is used in this function description.<br />

The function of the module is selected using a rotary switch<br />

behind the front cover between the series of switches.<br />

■ As shown in the following diagram set the function<br />

switches to the setting 8 x Output 8 x Input.<br />

<strong>Safety</strong> digital input module SM326<br />

Before installation, the PROFIsafe address must be set at the<br />

rear of the module according to HW Config.<br />

■ Set the DIL switches as shown in the following diagram.<br />

470 Functional Example No. SD-FE-I-001-V11-EN<br />

SINAMICS G120, CU240S DP F<br />

Two DIP switch blocks are located under the BOP (Operator<br />

Panel) in the upper section of the module.<br />

The upper DIP switch block is for general CU functions - and is<br />

not relevant for this function example.<br />

General I/O DIP switch<br />

0-20 mA<br />

ON<br />

OFF<br />

AI0<br />

AI1<br />

0-10 V<br />

24 V Encoder<br />

Supply<br />

5 V Encoder<br />

Supply<br />

Encoder A<br />

termination<br />

Encoder B<br />

termination<br />

Encoder Z<br />

termination<br />

The Profibus address of the SINAMICS G120 can be set using<br />

the lower DIP switch block. Alternatively, the PROFIBUS address<br />

can also be set using parameter p918. It should be noted<br />

that the setting using DIP switches has priority over parameter<br />

p918.<br />

■ Set the DIP switches to address 10 as shown in the following<br />

diagram.<br />

ON<br />

OFF<br />

PROFIBUS Address DIP switch<br />

(1) (2) (4) (8) (16) (32) (64)<br />

Bit 0<br />

Bit 1<br />

Bit 2<br />

Bit 3<br />

Bit 4<br />

Bit 5<br />

Bit 6