Ex. No.<br />

11 Process: Channel / module error<br />

(automatic reintegration)<br />

Precondition<br />

The user has set "ACK_NEC = 0" in the safety program.<br />

State<br />

F-module not passivated (1, 2)<br />

Error occurs<br />

F-module passivated (3, 4)<br />

Error removed<br />

F-module reintegrated (5)<br />

358 Functional Example No. AS-FE-I-011-V10-EN<br />

Process sequences<br />

If an error is pending at the F-module (channel or module error),<br />

the F-module is passivated by the F-system. If the error<br />

has been removed and "ACK_NEC = 0", the F-module of the<br />

F-system is automatically reintegrated.<br />

The following figure and table illustrates the process sequence.<br />

Numbers in brackets indicate the state.<br />

Description of status and events F-I/O-module data block / SF-<br />

LED<br />

A: ACK_NEC<br />

B: PASS_OUT<br />

C: QBAD<br />

D: SF-LED<br />

A B C D<br />

1 F-module is not passivated.<br />

Event: error occurs at the F-module.<br />

0 0 0 0<br />

2 F-module has recognized the error.<br />

Event: F-system recognizes the error at the F-module.<br />

0 0 0 1<br />

3 F-system has passivated F-module.<br />

Event: Removing the error at the F-module.<br />

0 1 1 1<br />

4 F-module has recognized that the error has been removed<br />

Event: F-system recognizes that the error at the F-module has been removed.<br />

0 1 1 0<br />

5 F-system has reintegrated the F-module. 0 0 0 0