Ex. No.<br />

4<br />

Unconditional trigger of safe standstill<br />

The output ENABLE_AXIS can be directly set to 0 via the input<br />

SAFE_STOP. This is achieved by setting SAFE_STOP to 0.<br />

PROFIsafe CRC<br />

PROFIsafe CRC<br />

The so-called PROFIsafe CRC has to be connected to the input<br />

FD_CRC_PSAFE [From Drive CRC PROFIsafe]. This CRC is defined<br />

by the redundant coarse position and the START-CRC in<br />

the SMx20 encoder module. The PROFIsafe CRC is simulated<br />

in the function block "F_DRIVE" and compared with the CRC already<br />

transmitted. To simulate the PROFIsafe CRC, encoder information<br />

such as the redundant coarse position data has to<br />

be transmitted to the formal operand FD_RED_ROUGH_POS<br />

and the START-CRC to the operand FD_START_CRC.<br />

Coarse position in relation to the redundant inverted coarse<br />

position<br />

In addition to the redundant coarse position, forwarded to<br />

FD_RED_ROUGH_POS, the standard coarse position information<br />

of the encoder has to be transferred to the relevant block<br />

parameter FD_ROUGH_POS. FB300 then checks whether<br />

these two values match.<br />

Stop categories<br />

The delay times for Stop categorie 1 are to be stored in the<br />

safety program by means of an application.<br />

In SIMOTION Version V4.0 / SINAMICS 2.4 or later, OFF 3 can<br />

be parameterized upon triggering of safe standstill stating a<br />

delay time for the safe standstill.<br />

454 Function Example No. MC-FE-I-004-V11-EN<br />

START-CRC<br />

The START-CRC is applied to parameter FD_STRT_CRC. The<br />

PROFIsafe CRC is again defined from the redundant coarse position.<br />

The START-CRC consists of the one-to-one NODE-ID of the SMx<br />

20 encoder module.<br />

This information avoids incorrect resp. double addressing,<br />

thus applying the PROFIsafe principle "Identification for transmitter<br />

resp. receiver".<br />

SIMOTION CRC<br />

The FD_SPEED_SIMO and FD_LIVE_SIGN data transmitted by<br />

the SIMOTION controller are saved by the SIMOTION function<br />

block using a CRC. This is expected at the input<br />

FROM_DRIVE_8 and simulated resp. compared in FB300.<br />

Version comparison<br />

The consistency of the function blocks "SIMOTION" and<br />

"Simatic F-CPU" is checked by means of a certain number before<br />

they can be used. The correct version of the SIMOTION<br />

function block has to be created at the input FD_VERSION<br />

[From Drive Version].