Ex. No.<br />

11 Description of the network function:<br />

The PASSIVATION_ON indicator light indicates that at least<br />

one channel of F DO and/or F-DI is passivated. Basically, there<br />

are two different methods to test whether at least one channel<br />

of a module is passivated:<br />

Method Advantage<br />

1 Polling all channels of the F-module:<br />

• for F-DI: via the "QBAD_I_xx" variables<br />

• for F-DO: via the "QBAD_O_xx" variables<br />

2 Polling the entire F-module:<br />

• via the "QBAD" variable.<br />

In the sample code both methods are used for demonstration<br />

purposes. "Method 2" can also be used here to detect whether<br />

the F-DO is passivated.<br />

FB3 / Network 2<br />

DB818.DBX 36.3<br />

Overview of the signals of the network:<br />

The F-Global data block (F_GLOBDB) is a fail-safe data block<br />

which contains all global data of the safety program as well as<br />

additional information for the F-system.<br />

Amongst other things, VKE0 and VKE1 provided there.<br />

Description of the network function:<br />

The passivated channels<br />

can be identified<br />

individually.<br />

Polling only possible<br />

once.<br />

Channel or module errors at the F-DI cause passivation of the<br />

F-DI at the entire module. After removing the error, the F-DI is<br />

automatically reintegrated.<br />

340 Functional Example No. AS-FE-I-011-V10-EN<br />

DB819.DBX 0.1<br />

Signal Source / Target Meaning<br />

F_GLOBDB.VKE0 From F-Global-DB Result of logic operation "0"<br />

F00001_4_8_F_DI_DC24V.ACK_NEC To F-I/O-module data block of F-DI F-DI is automatically reintegrated<br />

Warning<br />

Automatic reintegration is only permitted if an automatic<br />

startup of the plant is not possible after the error<br />

has been removed.