Ex. No.<br />

11 The user has only read access to the following variables in the<br />

F-I/O-module data block.<br />

Variable<br />

Which information does the user receive when reading the variables?<br />

(Type)<br />

PASS_ON<br />

(BOOL)<br />

QBAD<br />

(BOOL)<br />

ACK_REQ<br />

(BOOL)<br />

IPAR_OK<br />

(BOOL)<br />

DIAG<br />

(BYTE)<br />

QBAD_I_xx<br />

(BOOL)<br />

QBAD_O_xx<br />

(BOOL)<br />

Declaration<br />

Address<br />

352 Functional Example No. AS-FE-I-011-V10-EN<br />

Default value<br />

OUT 2.0 1 "PASS_OUT = 1":<br />

The F-I/O-module is passivated.<br />

Cause of the passivation:<br />

"F-communication error", "module error", "channel error" (see page 354).<br />

"PASS_OUT = 0 UND QBAD = 1":<br />

The F-I/O-module is passivated.<br />

Cause of the passivation:<br />

"PASS_ON = 1" was set in the safety program.<br />

Comment:<br />

Depending on the settings in the hardware configuration of STEP 7 the entire module or<br />

only faulty channels are passivated.<br />

OUT 2.1 1 "QBAD = 1":<br />

Currently the substitute value ("0") is used for at least one channel instead of the process<br />

value. Which channels are passivated is indicated via the QBAD_I_xx or QBAD_O_xx variables<br />

(see below).<br />

OUT 2.2 0 "ACK_REQ = 1":<br />

The error that caused the passivation has been removed.<br />

Acknowledgement for manual reintegration (ACK_REI) by the user is now possible.<br />

Cause of the passivation:<br />

"F-communication error", "module error", "channel error" (see page 354).<br />

Comment:<br />

If the error causing the passivation has been removed, and this has been recognized by<br />

the F-system, the F-system sets "ACK_REQ = 1".<br />

After acknowledgement by the user, the F-operating system sets "ACK_REQ = 0".<br />

OUT 2.3 0 Reconfiguration of fail-safe DP-standard slaves.<br />

OUT 3.0 0 Service information<br />

OUT 4.0 bis<br />

7.7<br />

OUT 8.0 bis<br />

11.7<br />

1 "QBAD_I_xx = 1":<br />

The input channel is passivated with number<br />

xx.<br />

The substitute value ("0") is used at input<br />

"xx".<br />

1 "QBAD_O_xx = 1":<br />

The output channel is passivated with number<br />

xx.<br />

The substitute value ("0") is used at output<br />

"xx".<br />

Comment:<br />

With the variables it can be detected<br />

which channels are passivated.<br />

The channel number xx has the value<br />

range: 00 to 31<br />

Example:<br />

"QBAD_O_00 = 1" means:<br />

Substitute value ("0") is currently output<br />

at output channel.