Behavior when the protective doors are opened<br />

When the protective doors are opened, it is initiated that the<br />

drive is shut down according to stop Category 1 in compliance<br />

with EN 60204-1. It must be ensured that potentially hazardous<br />

motion must have come to a standstill before a person can<br />

reach the potentially hazardous area!<br />

■ A 0 signal is entered at contact 65 (controller enable) of the<br />

drive via the enable contacts of safety combination A1. The<br />

drive is immediately braked down to 0 speed and the pulses<br />

are cancelled. The delay time of safety combination A1 is<br />

simultaneously started and the drive must have come to a<br />

standstill before it expires.<br />

Powering-up and powering-down the drive<br />

The drive can be started or stopped when the protective doors<br />

are closed.<br />

■ When the internal safety relay and the internal line contactor<br />

of the rectifier unit are in the correct state, safety combination<br />

A1 is brought into an operational state.<br />

■ The internal line contactor of the rectifier unit and the<br />

internal safety relay of the drive are energized.<br />

■ When pressing S2 ("On"), contactor K1 is energized and<br />

latches. A 1 signal is entered at contact 65 (controller<br />

enable) of the drive and the drive starts.<br />

■ The safely delayed enable contacts of safety combination<br />

A1 open after the selected delay time has expired. This<br />

means that the internal safety relay of the drive (1st shutdown<br />

path!) and the internal line contactor of the rectifier<br />

unit (2nd shutdown path!) are no longer energized.<br />

■ If the internal safety relay or the internal line contactors of<br />

the rectifier unit have not dropped-out because of incorrect<br />

behavior (e.g. fault), then their checkback signal contacts<br />

AS1/2 in the on circuit of the safety combination A1 are not<br />

closed. The safety combination cannot be switched-in.<br />

■ When button S1 ("Off") is pressed, contactor K1 is no longer<br />

energized and a 0 signal is entered at contact 65 (controller<br />

enable) of the drive. The drive is immediately braked down<br />

to 0 speed and the pulses are cancelled. If the protective<br />

doors are opened, the safely delayed enable contacts of<br />

safety combination A1 open after the selected delay time<br />

has expired. This means that the internal safety relay of the<br />

drive (1st shutdown path!) and the internal line contactor<br />

of the rectifier unit (2nd shutdown path!) are no longer<br />

energized.<br />

Functional Example No. MC-FE-I-002-V11-EN 419<br />