Ex. No.<br />

1<br />

Setup and Wiring<br />

In order to set up and wire the functional example, it is absolutely<br />

necessary to consider the following note:<br />

Warning!<br />

In order to meet the requirements of <strong>Safety</strong> Category<br />

4, it is obligatory to read back the process signal to<br />

the actuator. Read back is not implemented in this<br />

example.<br />

The actuator in this example is an indicator light simulating<br />

a machine. If other actuators are used, read<br />

back has to be ensured by the user. The <strong>Safety</strong> <strong>Integrated</strong><br />

Functional Example No. 7 „Integration of the<br />

Readback Signal in an Application of Category 4 acc.<br />

to EN 954-1“ provides a detailed description of "Read<br />

back".<br />

An overview of the hardware structure<br />

The arrangement to implement the emergency stop functionality<br />

consists of a PROFIBUS configuration. A failsafe S7-CPU is<br />

used as DP master, an ET 200M as DP slave. The ideally used<br />

indicator light simulates the hazardous "machine". The indicator<br />

light can be replaced by actuators in accordance with their<br />

requirements.<br />

PS<br />

307<br />

CPU<br />

315F<br />

IM<br />

153-2<br />

Acknowledge<br />

button<br />

(NO)<br />

<strong>Safety</strong><br />

protector<br />

DI<br />

SM321<br />

DI<br />

SM326<br />

DO<br />

SM326<br />

„Start“<br />

button<br />

(NO)<br />

Actuator<br />

optional<br />

NC / NC<br />

Emergency<br />

stop<br />

button<br />

172 Functional Example No. AS-FE-I-001-V10-EN<br />

Wiring of the hardware components<br />

Requirements: The power supplies are supplied with 230V AC.<br />

First check the addresses set at the hardware components<br />

listed below:<br />

Hardware<br />

component<br />

Address<br />

to be set<br />

Note<br />

IM 153-2 6<br />

(PROFIBUS<br />

adress)<br />

Can be changed<br />

DI (SM326) 8 You can change<br />

the address areas<br />

of the module<br />

via inputs<br />

(DIL button at<br />

the back of the<br />

module).<br />

Please note the<br />

following:<br />

During safety<br />

operation, input<br />

and output address<br />

have to be<br />

identical,<br />

divisible by 8<br />

and they must<br />

have a value<br />

between 8 and<br />

8176 (see<br />

screenshot).<br />

DO (SM326) 24 You can change<br />

the address areas<br />

of the module<br />

via inputs<br />

(DIL button at<br />

the back of the<br />

module).<br />

Please note the<br />

following:<br />

During safety<br />

operation, input<br />

and output address<br />

have to be<br />

identical,<br />

divisible by 8<br />

and they must<br />

have a value<br />

between 8 and<br />

8176 (see<br />

screenshot).<br />

Note<br />

The DP interface of the CPU 315F must be connected<br />

with the DP interface of the IM 153-2.