Ex. -No.<br />

4.3<br />

Description Parameters<br />

The external device monitoring circuit for a dependent, second OSSD<br />

has the same function as the standard external device monitoring<br />

circuit.<br />

This circuit monitors the second channel, but does not have any<br />

effect on the enabling of channel 1.<br />

In this example, the magnet contact is monitored by the second<br />

external device monitoring circuit.<br />

The Monitored start - monitor input device requires activation of the<br />

start input of the corresponding OSSD as an additional start requirement.<br />

If the AND link of all the monitoring, linking and external device<br />

monitoring circuit devices of an OSSD delivers an ON result, and if the<br />

start requirements have been fulfilled, the Monitored start - monitor<br />

input start device relays the enabling request to the output device.<br />

After the first output circuit is switched off, the second output circuit<br />

is switched on after the set delay time elapses. The delay time can<br />

be set between 1 s and 300 s in 1 s increments. The second output<br />

circuit must be switched off before the first output circuit is switched<br />

on.<br />

If the door is enabled, status ON, before the second output circuit is<br />

switched on, the first output circuit is switched on again and the second<br />

output circuit remains switched off.<br />

Unlocking function<br />

After the first output circuit is switched off via the door release and<br />

the set delay time has elapsed (or via the standstill monitor), the second<br />

output circuit switches on, so that in turn the doors are unlocked.<br />

This type of unlocking is not always desired.<br />

By activating the Unlocking device checkbox, a standard slave can<br />

be specified whose status (LOCK signal) determines whether or not<br />

the interlocking should remain after the delay time has elapsed.<br />

When the machine is switched off, the LOCK signal enables the door<br />

interlock to be switched on or off as desired.<br />