Behavior when Emergency Stop is issued<br />

Button S3 ("Emergency Stop") is used to initiate an Emergency<br />

Stop command. This initiates that the drive is shut down according<br />

to stop Category 1 in compliance with EN 60204-1.<br />

■ A 0 signal is entered, via the enable contact of safety combination<br />

A1, at contact X101.X (OFF3) of the drive. The<br />

drive is immediately braked down to 0 speed and the pulses<br />

are cancelled. At the same time, the drop-out delay of timer<br />

relay K2a and the delay time of the safety relay A1 are<br />

started; the drive must have come to a standstill before<br />

they expire.<br />

Behavior when the protective doors are opened<br />

When the protective doors are opened, it is initiated that the<br />

drive is shut down according to Stop Category 1 in compliance<br />

with EN 60204-1. It must be ensured that potentially hazardous<br />

motion must have come to a standstill before a person can<br />

reach the potentially hazardous area!<br />

■ A 0 signal is entered, via the enable contact of safety combination<br />

A2, at contact X101.X (OFF3) of the drive. The<br />

drive is immediately braked down to 0 speed and the pulses<br />

are cancelled. At the same time, the drop-out delay time of<br />

time relay K2a is started and before this time has expired,<br />

the drive must have come to a standstill.<br />

■ The internal safety relay of the drive is no longer energized<br />

after the drop-out delay time of time relay K2a has expired<br />

(1st shutdown path!).<br />

■ Before the selected delay time of safety combination A2<br />

has expired, the internal safety relay of the drive must have<br />

already dropped-out. Its checkback signal contacts<br />

X533.1/2 indicate that the drive is in a safe condition.<br />

Powering-up and powering-down the drive<br />

The drive can be started or stopped when the protective doors<br />

are closed and Emergency Stop button S3 is released.<br />

■ When pressing button S2 ("On"), safety combination A1 is<br />

brought into the operational state. Line contactor K1 is<br />

energized.<br />

■ When pressing button S2 ("On"), contactor K3 is energized<br />

and latches; time relay K2a is simultaneously energized.<br />

The internal safety relay is energized and a 1 signal is<br />

entered at contact X101.X (OFF3) of the drive. The drive<br />

restarts.<br />

■ The internal safety relay of the drive is no longer energized<br />

after the drop-out delay time of time relay K2a has expired<br />

(1st shutdown path!).<br />

■ After opening the safely delayed enable contact of safety<br />

combination A1, line contactor K1 is no longer energized<br />

and the drive is electrically isolated from the line supply<br />

(2nd shutdown path!).<br />

■ The checkback signal from line contactor K1 is monitored in<br />

the on circuit of safety combination A1. If the contactor<br />

does not drop-out due to an erroneous function, a restart<br />

after Emergency Stop is prevented.<br />

■ After the selected delay time has expired, the safely<br />

delayed enable contacts of the safety combination A2<br />

open.<br />

■ If the internal safety relay of the drive is functioning correctly,<br />

its checkback signal contact X533.1/2 is closed, line<br />

contactor K1 does not drop-out. If the internal safety relay<br />

does not function correctly, its checkback signal contacts<br />

X533.1/2 are not closed, line contactor K1 drops-out and<br />

isolates the drive from the line supply (2nd shutdown<br />

path!).<br />

■ When button S1 ("Off") is pressed, contactor K3 is no longer<br />

energized and the drop-out delay of time relay K2a is simultaneously<br />

started. When contactor K3 drops-out, a 0 signal<br />

is entered at contact X101.X (OFF3). The drive is immediately<br />

braked down to 0 speed and the pulses are cancelled.<br />

The internal safety relay of the drive is no longer energized<br />

after the drop-out delay time of time relay K2a has expired.<br />

The protective doors can be opened.<br />

Functional Example No. MC-FE-I-001-V11-EN 399<br />