Symbol Function Explanation<br />

START Push button (NO) 1: start request<br />

C_REQ_SG Mode switch Switch, which requests "safe speed" (SG) with "1" signal. Normal operation can only be started when<br />

this bit is on "0" signal.<br />

C_SW_FDO<br />

R<br />

Position switch 1: safety door closed<br />

IMPULSE_ Impulse release for See NW3<br />

RELEASE MASTERDRIVES<br />

STOP Push button (NC) 0: stop request<br />

C_NERR_ Error bit for switch-on This bit represents the status on a flip-flop in the F-program which safely switches MASTERDRIVES off<br />

ESTP_FDOR locking<br />

in the event of a failure. C_NERR_ESTP_FDOR=0, if at least one of the following events is true:<br />

• <strong>Safety</strong> door is opened during normal operation<br />

• Emergency stop push button is pressed<br />

• In operating mode "safe speed" (SG) the actual speed value exceeds a comparison value N_SG.<br />

• in "safe speed" (SG) mode, the actual speed value determined with PROFIBUS and the actual speed<br />

value determined with the ET 200S count module are deviating.<br />

• In operating mode "safe speed" (SG) the drive spins (SSTILL=0), even though no start request is<br />

pending (OUT1=0).<br />

• The readback signals from contactor K2 or option K80 are not pending correctly.<br />

C_EN_SG Enable "safe speed"<br />

(SG)<br />

1: operating mode "safe speed" (SG) active<br />

OUT1 Enable start of Parameter of MASTERDRIVES, controlled by S7-400 (Master-CPU) via PROFIBUS.<br />

MASTERDRIVES) "1" signal means: drive starts.<br />

OUT1=1 for the operating modes<br />

• Normal operation<br />

• Safe speed" (SG)<br />

OUT1=1 requires OUT3=1.<br />

C_OUT1 Enable start of<br />

MASTERDRIVES<br />

Information for the F-CPU<br />

Without the AND logic operation of C_EN_SG with L 254.4<br />

(OUT2) the drive would in operating mode "safe speed" (SG)<br />

not restart after standstill and pulse blocking. Reason: After<br />

pulse blocking MASTERDRIVES resets the Bit OUT2 internally<br />

to "0" signal and goes to "switch-on locking" mode. After<br />

pressing the dead man switch the safety relay of option K80 is<br />

controlled again, which causes MASTERDRIVES to reset the<br />

OUT2 bit to "1" signal. Only now must the start command assign<br />

"1" signal to the OUT1 bit.<br />

Note<br />

After unplugging the PROFIBUS connector from<br />

MASTERDRIVES (during runtime) the drives goes to<br />

standstill. Renewed starting requires pressing not only<br />

acknowledgement (ACK) but also the stop button<br />

(STOP) to reset OUT1 in the Master-CPU.<br />

Functional Example No. AS-FE-I-012-V10-EN 385<br />