MECON LIMITED<br />

REGD. OFF: RANCHI (BIHAR)<br />

PROCESS & PIPING<br />

DESIGN SECTION<br />

NEW DELHI<br />

TITLE PIPING FABRICATION AND<br />

ERECTION<br />

STANDARD SPECIFICATION<br />

SPECIFICATION NO. PAGE 51 OF 62<br />

MEC/S/05/62/06 REVISION 0<br />

• Equipment for cleaning <strong>of</strong> surface to be examined.<br />

• Rulers calibrated in centimeters for exact location <strong>of</strong> the position <strong>of</strong><br />

defects.<br />

The characteristics <strong>of</strong> the above-listed instruments and equipment shall<br />

guarantee:<br />

a) that the required standards <strong>of</strong> the inspection procedure, as previously<br />

established and approved by the COMPANY, are satisfied.<br />

b) continuous operation<br />

1.5 Ultrasonic Instruments<br />

All the instruments and equipment shall be approved by the COMPANY<br />

before being used. The COMPANY has the authority to reject any item<br />

which is considered unsuitable. The decision <strong>of</strong> the COMPANY is final.<br />

The CONTRACTOR appointed to carry out ultrasonic inspection shall<br />

also ensure the operational efficiency and maintenance <strong>of</strong> the<br />

instruments and equipment, and shall immediately substitute any item<br />

rejected by the COMPANY.<br />

All the instrument and equipment necessary for carrying out ultrasonic<br />

inspection on site shall satisfy the requirements laid down by the public<br />

board <strong>of</strong> institutions which regulate "safety at work".<br />

The ultrasonic instruments :<br />

• Shall be each pulse type, able to generate, receive and display, on the<br />

screen a cathode ray tube (CRT) pulse, at frequencies between 1 and 6<br />

mhz. The useful part <strong>of</strong> the CRT screen shall be at least 70m wide and at<br />

least 50mm high.<br />

• Shall have various amplification, with steps <strong>of</strong> 1 or 2 dB over a range <strong>of</strong> a<br />

least 60 dB.<br />

• The regulation control shall be accurate to within 1 dB and this accuracy<br />

shall be certified by the instrument manufacturer.