MECON LIMITED<br />

Delhi<br />

PROCESS & PIPING<br />

DESIGN SECTION<br />

TECHNICAL SPECIFICATION FOR<br />

TEMPORARY CATHODIC<br />

PROTECTION SYSTEM<br />

TECHNICAL SPECIFICATION NO. : MEC/TS/05/62/016A REV-1 Page 6 <strong>of</strong> 19<br />

As far as possible equipment including test stations, anode lead junction boxes, etc.,<br />

shall be located in safe area. All equipment located in hazardous areas shall be <strong>of</strong><br />

flame pro<strong>of</strong> type as per IS:2148 for gas groups <strong>II</strong>A & <strong>II</strong>B and temp. class T3.<br />

6.1 Anode Ground Beds<br />

6.1.1 The pipeline shall be protected by prepacked zinc/ magnesium anodes.<br />

6.1.2 Anodes shall be installed along the pipeline at suitable intervals as per pipeline protection<br />

voltage attenuation calculations and ground bed resistance/ current output <strong>of</strong> anode<br />

installations. Minimum one anode installation shall be provided for every one km. <strong>of</strong> the<br />

pipeline. In congested area, minimum one anode installation shall be provided for every<br />

250 meter <strong>of</strong> pipeline length.<br />

6.1.3 Each electrically continuous section <strong>of</strong> pipeline shall preferably be protected totally by one<br />

type (material) <strong>of</strong> anodes to avoid inter-anode circulation currents.<br />

6.1.4 The anodes shall be installed at sufficient depth to reach moist soil and shall be<br />

separated from the pipe line by at least 5m and 2m for magnesium and zinc anodes<br />

respectively. The anode connections to pipeline shall be routed through test stations.<br />

6.1.5 At the temporary cathodic protection anode ground bed, the leads <strong>of</strong> all the anodes shall<br />

be joined together in a junction box filled with epoxy and buried. A single cable shall be<br />

routed from the junction box to the test station. At permanent CP anode ground bed (i.e.<br />

at cased crossing), the leads <strong>of</strong> all the anodes shall be brought up to the test station and<br />

shall be terminated individually.<br />

6.1.6 For sacrificial anode ground bed which shall be integrated with permanent CP System the<br />

leads <strong>of</strong> all the anodes shall be brought up to the test station and shall be terminated<br />

individually.<br />

6.1.7 The number <strong>of</strong> anodes at each ground bed shall be sufficient for providing the specified<br />

pipe protection current density taking into consideration the ground bed resistance, pipe<br />

coating resistance, cable resistance, etc. Contractor shall prepare a table for number <strong>of</strong><br />

anodes required at different soil resistivities to produce the specified protection current.<br />

6.2.1 Magnesium anode<br />

The anode shall be <strong>of</strong> high manganese, magnesium alloy packed with special back fill.<br />

The metallurgical composition, potential and consumption rate <strong>of</strong> anode shall be as<br />

below:<br />