TABLE 13.0 : COATING SYSTEM FOR EXTERNAL SIDE OF UNDERGROUND CARBON STEEL PLANT<br />

PIPING AND TANKS<br />

S. NO. DESIGN TEMPERATURE SURFACE PREPARATION<br />

PAINT SYSTEM<br />

IN °C<br />

PRIMER FINISH PAINT<br />

13.1 CARBON STEEL PLANT PIPING (UNDERGROUND)<br />

13.1.1 YARD COATING<br />

13.1.1.1 25 TO 60 SSPC-SP-10 1 COAT OF 4mm THICK COALTAR<br />

SYNTHETIC FAST COATING WRAPPING<br />

DRYING PRIMER AS PER AWWA-C-203<br />

TYPE-B AS PER IN 2 LAYER OF EACH<br />

AWWA-C-203 (1991) 2mm THICKNESS<br />

13.1.2 OVER THE DITCH COATING<br />

13.1.2.1 25 Tto 60 SSPC-SP-10 1 COAT OF 2 LAYERS OF 4 mm<br />

SYNTHETIC FAST COALTAR BASED<br />

DRYING PRIMER TAPE COATING AS<br />

TYPE-B AS PER PER AWWA-C-203 &<br />

AWWA-C-203 (1991) AS PER SMMS EIL<br />

SPEC. 6-06-203-REV.2<br />

13.2 CARBON STEEL PLANT PIPING (UNDERGROUND)<br />

13.2.1 61 TO 400 SSPC-SP-10 1 COAT OF F-9 @<br />

65-75µ DFT/ COAT<br />

NONE 65-75<br />

13.3 EXTERNAL SIDE OF UNINSULATED UNDERGROUND STORAGE TANKS:<br />

13.3.1 40 TO 80 SSPC-SP-10 1 COAT OF F-9 @ 3 COATS OF F-7 @ 365<br />

65-75µ DFT/ COAT 100µ DFT/ COAT<br />

3 X 100 = 300<br />

13.3.2 -90 TO –41<br />

SSPC-SP-10 1 COAT OF F-9 @ NONE<br />

65-75<br />

81 TO 400° c<br />

65-75µ DFT/ COAT<br />

1 COAT OF<br />

AMERCOAT 738 @<br />

250µ DFT/ COAT<br />

NONE<br />

250<br />

Page 30 <strong>of</strong> 49<br />

TOTAL DFT IN<br />

MICRONS (MIN.)<br />

REMARKS<br />

4mm CTE coating shall<br />

confirm to 120/ 5 as<br />

per BS: 4164