<strong>Rexroth</strong> <strong>Indra<strong>Drive</strong></strong> Mounting and Installation 6-27<br />

DOK-INDRV*-FU*********-IB01-EN-P<br />

Badly grounded control cabinet doors act as antennas. It is recommended<br />

to connect the doors to the control section on top, in the middle and on<br />

the bottom via short equipment grounding conductors with a cross section<br />

of at least 6 mm 2 or, even better, via grounding straps with the same<br />

cross section. Make sure connection points have good contact.<br />

Fig. 6-31: Separation of interference-free area and interference-susceptible<br />

area in control cabinet