6-30 Mounting and Installation <strong>Rexroth</strong> <strong>Indra<strong>Drive</strong></strong><br />

Influence of the Motor Power<br />

Cable<br />

Routing the Motor Cables<br />

cable duct 1:<br />

mains connection<br />

lines<br />

Design and Installation in Strongly Interference-<br />

Susceptible Area of Control Cabinet (Area C)<br />

Area C mainly concerns the motor cables, especially at the connection<br />

point at the device.<br />

The discharge capacitance is limited to ensure compliance with the limit<br />

values. The calculation of the discharge capacitance can be found in the<br />

"Calculations" chapter.<br />

If the applications allows this, the cable length should always be kept<br />

short. Avoid unnecessary line lengths.<br />

The motor cables have to be run in shielded form. Besides they are<br />

always to be routed with a distance of d5 = 100 mm to the other<br />

interference-free lines and to signal cables and lines, or to be separated<br />

from them by a grounded distance plate. The latter is not required for the<br />

feedback cables of <strong>Rexroth</strong> motors.<br />

At the drive controller connection the motor cables and the (unfiltered)<br />

power connection lines may only be routed in parallel for a distance of<br />

300 mm. After that distance, motor cables and power supply cables have<br />

to be routed in opposite directions in separate cables ducts, as illustrated<br />

in the following figures (Fig. 6-32; Fig. 6-33) by the example of a drive<br />

system with separate mains connection per drive axis <strong>Indra<strong>Drive</strong></strong> HCS.<br />

Area B drive controllers<br />

Area C<br />

motor cable:<br />

shield contact via clips at least at one point:<br />

alternatively at device or on mounting plate at<br />

control cabinet outlet<br />

parallel routing:<br />

length max. 300 mm<br />

cable duct 2:<br />

motor cable<br />

with a distance of at least 100 mm<br />

or separated by grounded<br />

distance plate<br />

Fig. 6-32: Option 1: separate routing of motor cable and mains connection lines<br />

via 2 cable ducts<br />

DOK-INDRV*-FU*********-IB01-EN-P