<strong>Rexroth</strong> <strong>Indra<strong>Drive</strong></strong> Diagnostic and Service Functions 8-35<br />

Possible Problems during Firmware Replacement<br />

Problematic Situations<br />

Requirements for Loading the<br />

Firmware<br />

Firmware Replacement in<br />

Control Section in the Case of<br />

Error<br />

DOK-INDRV*-FU*********-IB01-EN-P<br />

Firmware replacement is carried out incompletely if one of the following<br />

situations occurs during the sequence of firmware replacement:<br />

• 24V supply of control section is switched off<br />

• connection to drive is interrupted (e.g. defective interface cable)<br />

• software crashes<br />

The drive controller then possibly is no longer operable because the<br />

firmware contained in the components is no longer compatible.<br />

If there isn't any valid firmware available in the control section in this case,<br />

the loader is started. The drive display signals "LOADER". The loader only<br />

allows updating the firmware of the control section. Optional cards, such<br />

as "safety technology I/O" (S1) or "cross communication" (CCD) cannot<br />

be programmed in this status. This must be done, after successful<br />

firmware replacement in the control section, in a second run according to<br />

the descriptions of the firmware replacement variants.<br />

In this situation, replacement of the control section firmware is only<br />

supported by IndraWorks D.<br />

Note: Upon successful firmware replacement in the control section,<br />

a restart has to be carried out. Then all available components<br />

have to be updated, too.<br />

The following requirements must have been fulfilled for loading firmware<br />

to the drive:<br />

• serial connection to drive available<br />

• drive display signals "LOADER"<br />

The following steps are required for loading the firmware to the control<br />

section in the case of error:<br />

1. Call IndraWorks D.<br />

2. In menu call firmware management under "Extras →<br />

Extras → <strong>Drive</strong> → Firmware management".<br />

3. Select device and COM interface.<br />

→ A new window opens and firmware available in current firmware<br />

directory is displayed on its left side.<br />

4. Highlight new firmware (*.ibf file) on left side and start firmware<br />

download via "Download" button.<br />

→ Firmware download runs automatically and all required firmware<br />

components are loaded to drive.<br />

5. After firmware download has been completed, close "Firmware<br />

management" window.<br />

6. Restart drive.<br />

If drive has not been equipped with optional cards, such as "safety<br />

technology I/O" (S1) or "cross communication" (CCD), continue following<br />

instructions for release update or version upgrade! Otherwise, carry out<br />

release update or version upgrade again to program optional cards.