<strong>Rexroth</strong> <strong>Indra<strong>Drive</strong></strong> Electrical Data 5-25<br />

10000<br />

W [kWs]<br />

1000<br />

P_s [kW]<br />

100<br />

10<br />

DOK-INDRV*-FU*********-IB01-EN-P<br />

Braking resistors for HCS03 ... 0210<br />

Peak power P_s and Energy absorption W<br />

1<br />

1 10 100 1000<br />

Duty cycle [s]<br />

Energy<br />

HLR01.1N-36K0-N05R4<br />

HLR01.1N-23K0-N05R5<br />

HLR01.1N-17K0-N05R1<br />

HLR01.1N-12K5-N05R5<br />

HLR01.1N-06K5-N06R1<br />

Power<br />

HLR01.1N-36K0-N05R4<br />

HLR01.1N-23K0-N05R5<br />

HLR01.1N-17K0-N05R1<br />

HLR01.1N-12K5-N05R5<br />

HLR01.1N-06K5-N06R1<br />

Fig. 5-36: Selection aid for braking resistors for HCS03.1E-W0210<br />

Line Cross Sections for Reinforced Braking Resistors<br />

HLR01.1<br />

According to the standards "Electronic equipment for use in power<br />

installations" (EN 50178, chapter 5.3.2.1) and "Adjustable speed electrical<br />

power drive systems" (EN 61800-5-1, chapter 4.2.5.4.2), a stationary<br />

connection of the equipment grounding conductor is required. The<br />

following requirement has to be complied with: cross section of equipment<br />

grounding conductor at least 10 mm 2 (mechanical stability).<br />

Note: For the equipment grounding conductor run lines with a cross<br />

section corresponding to that of the lines for mains connection<br />

at the drive controller HCS and having at least 10 mm 2 .<br />

Requirements for line routing:<br />

• The cross sections are valid for one phase each in the case of<br />

stranded wires and are specified according to the regulations of<br />

VDE0298.<br />

• Up to 50 mm 2 , solid wires in the cable duct.