7-56 Commissioning and Parameterization <strong>Rexroth</strong> <strong>Indra<strong>Drive</strong></strong><br />

Function<br />

Function<br />

Function<br />

Function<br />

Function<br />

See also Functional Description "Position Control with Cyclic Command<br />

Value Input"<br />

P-0-0063, Torque-generating voltage, actual value<br />

Input min/max: Default value: Unit:<br />

MPB: --- / --- --- V eff<br />

Display parameter for the torque-generating component of the voltage<br />

output by the current loop. The value is updated with the current loop<br />

cycle time.<br />

P-0-0064, Flux-generating voltage, actual value<br />

Input min/max: Default value: Unit:<br />

MPB: --- / --- --- V eff<br />

Display parameter for the flux-generating component of the voltage output<br />

by the current loop. The value is updated with the current loop cycle time.<br />

P-0-0065, Absolute voltage value, actual value<br />

Input min/max: Default value: Unit:<br />

MPB: --- / --- --- V eff<br />

This parameter displays the absolute value of the voltage output by the<br />

current loop which consists of the voltage components Ud and Uq.<br />

Note: The displayed voltage value corresponds to the measured<br />

value available at the motor terminals (conductor reference)<br />

and is updated with the current loop cycle time!<br />

See also Functional Description "Motor Control"<br />

P-0-0067, Phase current U, actual value<br />

Input min/max: Default value: Unit:<br />

MPB: --- / --- --- A<br />

This parameter is used to display the actual current value in the motor<br />

phase U measured in the current loop clock (TA, current).<br />

See also Functional Description "Performance Data"<br />

P-0-0068, Phase current V, actual value<br />

Input min/max: Default value: Unit:<br />

MPB: --- / --- --- A<br />

This parameter is used to display the actual current value in the motor<br />

phase V measured in the current loop clock (TA, current).<br />

See also Functional Description "Performance Data"<br />