<strong>Rexroth</strong> <strong>Indra<strong>Drive</strong></strong> Commissioning and Parameterization 7-9<br />

Default Settings in the Motor Encoder Data Memory ("Load Defaults<br />

Procedure")<br />

Initial Commissioning<br />

Recommissioning<br />

DOK-INDRV*-FU*********-IB01-EN-P<br />

Loading Basis Parameter<br />

The following <strong>Rexroth</strong> housing motors are equipped with an encoder data<br />

memory:<br />

• MHD, MKE, MKD<br />

• MSK, MSH, MAD, MAF, MAL<br />

Note: The <strong>Bosch</strong> motor with the type designation "SF..." that can be<br />

operated with <strong>Indra<strong>Drive</strong></strong> controllers is equipped with an<br />

encoder data memory, too. As regards commissioning and<br />

parameters, SF motors have the same behavior as <strong>Rexroth</strong><br />

housing motors with encoder data memory!<br />

Notes on Commissioning<br />

In the case of <strong>Rexroth</strong> housing motors with encoder data memory, the<br />

values for the motor parameters stored in the encoder, the measuring<br />

system parameters and, where required, the motor holding brake<br />

parameters are automatically loaded to the controller when the drive is<br />

switched on.<br />

At the initial commissioning of a drive the F2008 RL The motor type has<br />

changed. error message will appear. This message only means that this<br />

motor has not yet been connected to the controller.<br />

By clearing this error message (reset via control panel or S-0-0099,<br />

C0500 Reset class 1 diagnostics) S-0-0262, C07_x Load defaults<br />

procedure command is automatically started. Default control loop<br />

parameter values for this motor are thereby loaded.<br />

Note: Depending on the setting in P-0-4090, Index for C07 Load<br />

defaults procedure, the following parameter values are<br />

loaded with the "load defaults procedure" command<br />

(S-0-0262):<br />

- default control loop parameter values (default setting)<br />

- basic parameter values (default parameter set) of the<br />

firmware.<br />

In the case of motors with integrated holding brake, the type of motor<br />

holding brake and the activation of the brake control is automatically set in<br />

P-0-0525, Holding brake control word.<br />

In the case of motors with several cooling type variants (MHD, MKD), the<br />

load data can be referred to the cooling type realized by entering the<br />

corresponding value in P-0-0640, Cooling type.<br />

When the machine is repaired the motor can be replaced by a motor of<br />

the same type without any problem. The adjustment to the controller does<br />

not need to be repeated. In the case of an absolute motor encoder, it is<br />

only necessary to make an adjustment to the machine axis by<br />

establishing the position data reference.<br />

If the motor type connected to the controller has changed, the controller<br />

signals this with F2008 RL The motor type has changed. and requests<br />

the default control loop parameter values and the motor type parameter to<br />

be loaded. In the case of a desired motor change, initial commissioning of<br />

the new axis motor is necessary. Otherwise there is an assembly error<br />

that has to be corrected!