<strong>Rexroth</strong> <strong>Indra<strong>Drive</strong></strong> Diagnostic and Service Functions 8-29<br />

Firmware Version Upgrade<br />

DOK-INDRV*-FU*********-IB01-EN-P<br />

3. Check safety technology parameters (only when safety technology<br />

has been activated in drive)<br />

In the case of a firmware release update, safety technology parameters<br />

are retained. With safety technology activated, the following steps are<br />

additionally required:<br />

Check whether correct safety technology parameters for drive are still<br />

⇒<br />

available.<br />

To do this, check the following points:<br />

• data in P-0-3205, Safety technology device identifier<br />

• status of safety technology via P-0-3207, Safety technology<br />

password level (in the case of active and locked safety<br />

technology, level is 2)<br />

• change counter of safety technology memory (P-0-3201, Change<br />

counter of safety technology memory)<br />

• operating hours at last change of memory (P-0-3202, Operating<br />

hours at last change of memory)<br />

When firmware in a drive controller is replaced by firmware of a new<br />

version, this is called firmware version upgrade (e.g.<br />

FWA-INDRV*-MPH-03V20-D5 replaced by FWA-INDRV*-MPH-<br />

04V08-D5).<br />

Note: Before carrying out the firmware version upgrade, you must<br />

save all parameters (e.g. with IndraWorks D). After firmware<br />

replacement the parameters must be restored because the<br />

command "C07_1 Load defaults procedure command" is<br />

carried out automatically. After the desired parameter file was<br />

loaded, the drive controller is ready for operation again.<br />

The described sequences of the firmware version upgrade depend on the<br />

configuration of the control section and the firmware used. The basically<br />

recommended sequence of the firmware version upgrade is illustrated in<br />

the scheme below: