7-102 Commissioning and Parameterization <strong>Rexroth</strong> <strong>Indra<strong>Drive</strong></strong><br />

Function<br />

Function<br />

Function<br />

Note: "Slip" is the difference of the rotational frequency of the electric<br />

rotary field in the stator divided by the number of pole pairs of<br />

the motor and the mechanical rotational frequency of the rotor.<br />

The value for P-0-4043 is motor-specific and for asynchronous <strong>Rexroth</strong><br />

motors is made available via the commissioning software (e.g.<br />

IndraWorks) or via the Intranet output of the manufacturer-side data base<br />

<strong>Drive</strong>Base!<br />

P-0-4045, Maximum possible continuous current<br />

Input min/max: Default value: Unit:<br />

MPB: --- / --- --- A eff<br />

This parameter indicates how much current the controller can<br />

continuously provide in the present load situation. At the same time, this<br />

current is the current to which the continuous current limitation would<br />

reduce, if the load situation would continue.<br />

See also Functional Description "Current Limitation"<br />

P-0-4046, Effective peak current<br />

Input min/max: Default value: Unit:<br />

MPB: --- / --- --- A eff<br />

This parameter displays the maximum current that the controller can<br />

temporarily supply to the motor in the active load condition. This is the<br />

rms value of the total current, i.e. torque-generating and magnetic-fieldgenerating<br />

components are contained!<br />

See also Functional Description "Current Limitation"<br />

P-0-4065, Non-volatile memory active<br />

Input min/max: Default value: Unit:<br />

MPB: --- / --- 2 --<br />

This parameter contains information on the active, non-volatile memory.<br />

The parameter values and, in the case of control voltage failure, the retain<br />

data are stored in the active memory.<br />

Meaning of the value:<br />

• 1: MultiMediaCard (MMC) is the active, non-volatile memory<br />

• 2: internal, non-volatile memory is active<br />

See also Functional Description "Parameters, Basics"<br />

P-0-4068, Field bus: control word IO<br />

Input min/max: Default value: Unit:<br />

MPB: --- / --- 0 --<br />

DOK-INDRV*-FU*********-IB01-EN-P